Greenheck Melink IH3 Operations User Manual
Page 16

SY‐09
Analog Output Source
None
List All Programmed Primary, Aux, and External
Airflows
SY‐10
Analog Input Function
SY‐11
Bypass Timer
10 minutes
30 sec, 1 min, 5 min, 10 min, 20 min, 30 min, 1 hr, 2
hr, 4 hr
SY‐12
Optic Hang Time
15 seconds
5, 10, 15, 30, 60, 90, 120, 180, 240, 300
SY‐13
Fan Speed Reporting Method
Feedback
VFD Feedback, Command Speed
SY‐14
Temperature Alarm Auto On
200
Not Used, 100F, 125F, 150F, 200F, 250F, 300F
SY‐15
Temperature Alarm Auto Off
Not Used
Not Used, On‐10, On‐20, On‐30,
SY‐16
Temperature Alarm Tone
No
Yes or No
SY‐17
Temperature Alarm Hoods to
Activate
All
All Hoods, Hood Group, Hood Only, None
SY‐18
Data Log Sample Rate, Speed
5 minutes
10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min
SY‐19
Data Log Sample Rate, Temperature
5 minutes
10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min
SY‐20
Data Log Sample Rate, Optics
5 minutes
10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min
SY‐21
Auto On, Manual Off, Delay Time
2 minutes
10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min
SY‐22
Unit Display
12H/F
12H/F, 24H/F, 12H/C, 24H/C