Optional accessories – Greenheck ERCH - Energy Recovery Unit with Packaged DX (468151) User Manual
Page 16

16
Energy Recovery Unit with Packaged DX
OPTIONAL ACCESSORIES
Variable Frequency Drives for Energy Recovery Wheel
Factory installed VFD for the energy recovery wheel are programmed at the factory per the settings shown
below . Refer to the instruction manual that ships with the unit when making adjustments . A copy of the manual
can be found online at www .drives .com . For technical support, contact yaskawa direct at 1-800-927-5292 .
Parameter
Setting
n01
Access Level
1
n30
Ref Upper Limit
100% or 66%*
n32
Motor Rated FLA
Motor FLA
n33
Elect Thermal Overload
1
n36
Multi-Function input (terminal S2)
10
n40
Multi-Function output (MA,MB,MC)
4
n41
Analog Freq . Reference Gain
0
n42
Analog Freq . Reference Bias
99
n46
Carrier Frequency
2
n58
Frequency Detection Level
20
n01
Access Level
0
Yaskawa GPD-305 Drive
*36 inch wheel is 66% (40Hz) . All other wheels are 100% (60Hz) .