Energy Recovery Unit with Packaged DX

Symptom

Possible Cause

Corrective Action

Compressor

will not run

or

does not

try to start

Open disconnect switch or circuit breaker .

Close switch and / or breaker .

Compressor contactor not closing .

Check voltage to contactor coil, transformer,
slave relay, system . Replace parts as necessary .

Blown fuse or tripped breaker .

Check for reason and repair . Replace fuse after
correcting problem .

Low line voltage .

Check line voltage . If more than 10% from
compressor marking, correcting is necessary .

Compressor motor protector open .

Motor thermal protector automatically resets .
Allow time (2 hrs .) for compressor to cool down
so protector will reset . Restart and check for
reason overheat occurred .

Compressor defective .

Check motor for open circuit, short circuit,
grounded windings or burn out .
Compressor may be seized; check refrigerant .
If necessary, replace compressor .

High or low pressure switch open or defective .

If manual reset (high pressure), reset switch .
(Switch opens at 400 psi and will not reset
above 250 psi for R22 or 600/420 respectively
for R410a) .
If auto reset (low pressure) does not reset and
everything else is OK, replace switch .

Open room thermostat or control
(no cooling required) .

Check room temperature . If temperature is
proper, wait for thermostat to close .

Loose wiring .

Check all wire terminals and tighten as
necessary .

Compressor starts

but cuts out on low

pressure

Low pressure

switch activates

at 25 psig for R22,

50 psig for R410a

Low refrigerant charge .

Check refrigerant pressures .

Airflow restricted .

Check for dirty evaporator coil, dirty filters,
dampers closed, iced evaporator coil, improper
belt, check motor amps, check duct design .

Restriction in refrigerant line .

Check refrigerant pressure, check and adjust
thermal expansion valve . If not functioning
properly, check for pressure drop across the
filter drier .

Defective low pressure switch .

Replace .

Troubleshooting – General Refrigeration Circuit

IMPORTANT TROUBLESHOOTING

NOTE!

Before any components are changed on the

refrigeration system, the cause of the failure must be

identified . Further problems will exist unless the true

cause or problem is identified and corrected .

IMPORTANT!

Do not release refrigerant to the atmosphere! If

required service procedures include the adding or

removing of refrigerant, the service technician must

comply with all federal, state and local laws . The

procedures discussed in this manual should only be

performed by a qualified HVAC Technician .

NOTE: Unit is equipped with a phase loss/phase reversal control . If system does not start, check phase of electrical supply .

Always have a completed Pre-Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.