Greenheck Vari-Green Control - Indoor Air Quality - VOC (I475407) User Manual

Page 6

Advertising
background image

6

Fan Cutout, Parameter P3
Factory Default = 0
0 – Fan Cutout Disabled
1 – Fan Cutout Enabled
The Fan Cutout is designed to shut off the exhaust

fan when the VOC level falls below the Air Quality

Setpoint.
With the Fan Cutout Enabled, when the %VOC

measurement is 2% below the Air Quality Setpoint

(as set by Parameter P0), the Fan Cutout timer is

activated and the dot on the display will flash. After

the Cutout Time has elapsed (as set by Parameter

P4), the Fan Speed Output on the controller will go

to 0 Volts, shutting off the exhaust fan. The Fan Icon

on the display will extinguish and the Dot will be on

steady.
When the %VOC measurement rises 5% above the

Air Quality Setpoint, the controller leaves Fan Cutout

mode and returns to normal operation. The Dot will

extinguish and the Fan Icon will turn on.

Fan Cutout Timer, Parameter P4
Factory Default = 30 Seconds
0 to 300 seconds in 1 second increments
See Parameter P3 for operational details

Output Override Percent, Parameter P5
Factory Default = 100%
20% to 100% in 1% increments
During normal operation, when the remote override

switch is closed, the Fan Speed Output on the

controller will immediately ramp to the P5 Output

Override Percent and stay there until the remote

override switch is opened. The remote override

can be activated by any normally-open voltage-free

contact. (See Wiring Diagram on pg. 7.) Closing the

contact will activate the override.
When the override is activated, the Fan Icon on the

display will turn on and the

minor display will show %OVR

and the main display will show

the Fan Speed Output percent

value.

Output State, Parameter P6
Factory Default = 1
0 – Manual Control
1 – Normal Operation
The Output State allows manual control of the Fan

Speed for system setup and commissioning tests.

Exiting this parameter returns the controller to

normal operation.
When entering this parameter, the value will be 1

(normal operation). Press the Down program switch

to set the parameter value to 0 and then press the

Enter program switch. The unit is now in Manual

Control.
The major display will read 50 for

50% output (5 VDC output). The

minor display will show %SPD.
Pressing the Up program switch

increases the displayed value

and proportionally increases the

Fan Speed Output from the controller. Pressing the

Down program switch decreases the displayed value

and proportionally decreases the Fan Speed Output.
The Fan Speed can be set to any value from 20% to

100% (for 2 to 10 VDC Fan Speed Output) or it can

be set to 0 for 0 VDC Fan Speed Output.
The Fan Speed will remain at the displayed value

until the Output State Parameter is returned to

Normal Operation mode.

Output Minimum, Parameter P7
Factory Default = 20%
20 to 100% in 1% increments
Sets the controller’s minimum Fan Speed Output

level.
Note: the controller will not allow the output minimum

to be set higher than the output maximum.

Output Maximum, Parameter P8
Factory Default = 100%
20 to 100% in 1% increments
Sets the controller’s maximum Fan Speed Output

level.
Note: the controller will not allow the output

maximum to be set lower than the output minimum.

Advertising