7

Wiring Diagram

Problem

Fan always at minimum speed

Place an opened permanent or white board marker underneath the controller. The

fan should increase speed within a few minutes.

Check that the air quality measurement is decreasing. If there is a large

contamination it may take a while to exhaust the VOCs.

Setpoint may be too low for persistent background VOCs.

Check the space for a spill.

Setpoint may be too low for persistent background VOCs.

If the controller will not turn the fan off, verify that the measured %VOC is at least

2% below set point. Verify that the cutout timer has started by looking for the

flashing dot.

If the controller will not restart the fan, verify that the measured %VOC is at least

5% above the setpoint.

Fan always at high speed

Fan Cutout not working properly

Potential Solution

Troubleshooting