Troubleshooting

4.1 HumSpot

Error message

Possible causes

Possible solutions

BUS ERR

1. The HumCenter is switched off.

2. Bus communication error (wiring

error) between HumSpot and
HumCenter

3. No bus ID or wrong bus ID entered in

HumSpot.

4. Bus ID assigned to a unit without

HumCenter.

1. Check the electricity supply to

the HumCenter.

2. Check the bus connection at

HumSpot and HumCenter.

3. Check the bus ID at HumSpot.

4. Set the bus ID to 0.

CAP ERR

1. Capability error: HumSpot does not

have current firmware.

2.

1. Install the current firmware in the

HumSpot.

2.

No HPS

1. No HPS has been assigned to the

HumSpot

2.

1. Assign an HPS to the HumSpot

using the HumCenter.

2.

SENS ERR

1. Hygrostat malfunction.

1. Replace the sensor.

MAX ERR

1. Maximum hygrostat has triggered

due to high room humidity.

2.

1. Check maximum hygrostat is

functioning.

2. Check hygrostat is functioning.

3. Adjust target value of maximum

hygrostat.

HPS ERR

1. No release received from HPS

(timeout).

1. Check if the HPS is

malfunctioning.

2. Check the wiring between the

HumSpot and HPS.