Modular Devices Transformer Sizing

120 / 24VAC

120 / 24VAC

120 / 24VAC

120 / 24VAC

80 VA

Transformer

Minimum

See Warning

Note Below

40 VA

Transformer

Minimum

See Warning

Note Below

100 VA

Transformer

Minimum

See Warning

Note Below

75 VA

Transformer

Minimum

See Warning

Note Below

Power/Comm

Board

Power/Comm

Board

Power/Comm

Board

Power/Comm

Board

Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.

Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.

A

A

A

A

12 Devices At 6 VA = 72 VA
Use 75 VA Transformer

6 Devices At 6 VA = 36 VA
Use 40 VA Transformer

16 Devices At 6 VA = 96 VA
Use 100 VA Transformer

13 Devices At 6 VA = 78 VA
Use 80 VA Transformer

6 Devices Maximum Per Branch Circuit

6 Devices Maximum Per Branch Circuit

Figure 15: Modular VAV/Zone Controller Actuator Package Transformer Sizing For Power/Comm Boards

Modular Devices - Transformer Sizing

Modular devices include the Modular VAV/Zone Controller Actuator

Package, Modular System Manager, and MiniLink Polling Device. All

of these devices can connect to each other and a Power/Comm Board

using prefabricated modular cables. See Figure 14 for Power/Comm

Board wiring and connections. When sizing transformers for these de-

vices, it is important to design your layout so that the fewest number of

Power/Comm Boards and the least number of transformers can be used.

In order to simplify wiring design and layout with modular devices, the

following rules apply:

1. Power/Comm Board maximum transformer size = 100 VA.

This is due to the board circuitry and fusing. Each modular

device is to be calculated at 6 VA. This allows for a

maximum of 16 devices per Power/Comm board. If more

than 16 devices are required, multiple Power/Comm boards

must be used. Any Slaved Zone actuators used are

considered a modular device and must be accounted for at

6 VA. each. They also must be included in the branch

circuit maximum quantity of 6. See rule #2.

2. No more than 6 modular devices allowed per branch circuit.

(Each Power/Comm board has 4 branch circuits

available on the board).

3. The longest total run per branch circuit is 240 feet. This is

due to voltage drop on the prefabricated cable. If cable runs

longer than 240 feet are required, additional Power/Comm

board(s) can be used. Each Power/Comm Board

connected that is in series with the first Power/Comm Board

would allow for an additional 240 feet of modular cable to

be added to the total cable run length.

See Figure 15 for information and some examples of transformer sizing

and branch circuit design.

Warning:

Do not ground the 24 V transformer that is to be

used with the Power/Comm boards. Grounding

of the transformer will damage the Power/Comm

board and all boards connected to it. A separate

transformer must be used for each Power/Comm

board. No exceptions. Do not connect any other

devices to the transformer for the Power/Comm

board.

15

Modular ZCAP Technical Guide

Installation & Wiring