Scheduling and operation modes, Scheduling, Modes of operation – Orion System Modular VAV/Zone Controller User Manual

Page 20: Sequence of operations, 20 modular zcap technical guide

Advertising
background image

Scheduling

Occupied/Unoccupied Mode

The VAV/Zone Controller monitors the communications loop for its Oc-

cupied and Unoccupied mode of operation command. Either the VAV/

Zone Controller Package or the GPC Plus can transmit the Occupied

command to the VAV/Zone Controller. This requires the Modular VAV/

Zone Controller Actuator Packages to all be connected to the system

communication loop through their RS-485 connector and to be properly

addressed for the command to be received.

Push-button Override Operation

During unoccupied hours, you can force the VAV/Zone Controller and

VCM-X Controller back to occupied operation by pressing the over-

ride button on the Modular Room Sensor or Digital Room Sensor. The

operation for the push-button override sequence is different depending

on which sensor you are using.

Modular Room Sensor

Pushing the override button for less than 3 seconds initiates the override

which will continue for a 2 hour duration. If during the override period

the button is pressed a second time for less than 3 seconds, an additional

2 hours will be added to the remaining override duration that is left at the

time of pushing the button. If the button is then depressed for more than

3 seconds anytime during the override duration, it cancels the override

and places the unit back into normal unoccupied operation.

Digital Room Sensor

Pushing the override button momentarily initiates the override which

will continue for a 2 hour duration. If during the override period the but-

ton is pressed a second time, it will cancel the override. If it is pressed

again, the override will be initiated again for a 2 hour duration. Every

other time the button is pushed, it cancels the override and places the

unit back into normal unoccupied operation.

Grouping Controllers For Overrides

On larger installations with several terminal units, the VAV/Zone Con-

trollers can be configured into groups so that an override generated by

one VAV/Zone Controller can cause several other controllers to follow

along and return to occupied mode for the programmed duration. Other

VAV/Zone Controllers not in the same group will simply maintain an

unoccupied damper or airflow setting as set by the user.

Push-button overrides are broadcast continuously by the initiating VAV/

Zone Controller until the controller itself times out or the override is

cancelled by the user. This broadcast forces the air handler to start its

main fan and provide cooling or heating, if so configured. It will re-

main on until the override broadcast has not been detected for at least

2 consecutive minutes.

Modes of Operation

There are 7 possible modes of operation for the HVAC Unit and the

VAV/Zone Controller. These modes are determined by the supply air

and/or space demand conditions. They are:

Supply Air Vent Mode

(Based on HVAC Unit SAT)

Space Vent Mode

(Based on VAV/Zone Controller Space Temp.)

Supply Air Cooling Mode

(Based on HVAC Unit SAT)

Space Cooling Mode

(Based on VAV/Zone Controller Space Temp.)

Supply Air Heating Mode

(Based on HVAC Unit SAT)

Space Heating Mode

(Based on VAV/Zone Controller Space Temp.)

Off Mode (Not displayed. See “Definitions of Modes”)

The process of determining each mode is in the following paragraph,

but the actual operation of each mode is explained in the sections that

follows.

Definitions of Modes

VAV & Zone Control Schemes

On all fan-powered and non-fan-powered terminal units, ‘VAV’ or ‘Zon-

ing’ supply air modes and space demands are calculated the same. If

the supply air temperature raises the deadband amount above the space

temperature, the supply air mode is heating. To cancel the supply air

heating mode, the supply air temperature must fall within 2 °F of the

space temperature. If the supply air falls the deadband amount below

the space temperature, the supply air mode is cooling. To cancel the

supply air cooling mode, the supply air temperature must rise within 2

°F of the space temperature. If the supply air is between the heating and

cooling deadband amounts, it is considered vent mode.

Supply Air Vent Mode

This mode occurs when the Supply Air Temperature is between the

heating and cooling setpoints.

Space Vent Mode

This mode occurs when the Space Temperature is between 0.5 °F below

the Cooling Setpoint and 0.5 °F above the Heating Setpoint.

Supply Air Cooling Mode

This mode occurs when the Supply Air Temperature falls to 1.0 °F below

the Space Heating Setpoint.

Space Cooling Mode

This mode occurs when the Space Temperature rises to 0.5 °F below

the Space Cooling Setpoint.

Supply Air Heating Mode

This mode occurs when the Supply Air Temperature rises to 1.0 °F above

the Space Cooling Setpoint.

Space Heating Mode

This mode occurs when the Space Temperature falls to 0.5 °F above the

Space Heating Setpoint.

Off Mode

During unoccupied mode, the mode is considered ‘OFF’ if the space

temperature does not generate a heating mode or cooling mode based

on the unoccupied heating & cooling setpoints.

Scheduling and Operation Modes

20

Modular ZCAP Technical Guide

Sequence of Operations

Advertising
This manual is related to the following products: