As with the Occupied Mode of operation, two different configurations

are available for the Unoccupied Space Heating mode. If the box is

configured to allow reheat during Supply Air Heating mode, the reheat

relays can be activated even when the HVAC unit is in the Supply Air

Heating mode. If the box is configured not to allow reheat when the

HVAC unit is in Supply Air Heating mode, the box heat relays will be

de-energized when the HVAC unit is in Supply Air Heating mode. In

either configuration, when the HVAC unit is in the Supply Air Heat-

ing mode, the damper will modulate open proportionally to the space

demand. The proportional window for the space temperature is 0.5 ºF

above to 1.5 ºF below the heating setpoint. This allows the space to take

advantage of the warm supply air in the duct.

If check for main fan status is not selected and the VAV/Zone terminal

unit has auxiliary heat (baseboard heat etc.) that does not require the

HVAC unit fan to operate, reheat can be used without the HVAC unit

fan operating. If check for main fan status is selected, the reheat will

only operate when the HVAC unit fan is operating.

The VAV/Zone Controller can activate auxiliary heating relays if the

Expansion Module has been connected and the correct number of heat-

ing stages (1, 2 or 3) has been configured. During demands for heat, the

first stage will activate whenever the space temperature drops below the

heating setpoint. The second stage will activate if the space temperature

falls 1.0 ºF below the heating setpoint. The third stage will activate if

the space temperature falls 2.0 ºF below the heating setpoint. There is a

two-minute delay between staging. This prevents stages from activating

at the same time. Once a heating stage has been activated, it must remain

on for at least one minute. Once it has been deactivated, it must remain

off for at least two minutes. The third stage relay will deactivate when

the space temperature rises to within 1.0 ºF of the heating setpoint. The

second stage relay will deactivate when the space temperature rises to

the heating setpoint. The first stage relay will deactivate when the space

temperature rises above the heating setpoint by 1.0 ºF. See Table 2:

Fan & Reheat Relay Staging for a complete layout of the various fan

& heat relay staging points.

Modulating (Proportional) Heat

The Modular VAV/Zone Controller Actuator Package also provides

an analog output for control of a modulating hot water valve or SCR

electric heater. It provides a 0-10 VDC signal to control the heating

device. When the space temperature drops to 0.5 ºF above the Heating

Setpoint, the output starts at 0 VDC and ramps up to 10 VDC at 1.5

below the Heating Setpoint.

Auxiliary Heat

The Auxiliary Heat option allows for a separate setpoint that is different

from the other heating setpoints. The Auxiliary Heat Relay energizes

at 0.5 ºF below the Auxiliary Heat Setpoint and de-energizes 0.5 ºF

above the Auxiliary Heat Setpoint. The Auxiliary Heat will continue

to function regardless of the HVAC Mode the VCM-X is in, or at any

airflow condition. This is typically used to control baseboard heat or an

external duct heater.

Series Flow Fan Terminals

If the VAV/Zone Controller has been configured as a Series Fan Powered

terminal unit, the series fan will run continuously when the VAV/Zone

Controller is in the Space Heating mode, no matter whether check for

main fan status has been selected or not. If the HVAC unit is in Supply

Air Heating mode, the damper will modulate to maintain the Space

Heating Setpoint.

Any series fan terminal unit that has check for main fan status selected

will also operate its series box fan anytime the HVAC unit controller is

broadcasting that the HVAC unit fan is operating, regardless of whether

it is calling for heat or not. The damper will be held at the closed posi-

tion until the main fan status broadcast is received. Once the broadcast

is received, the damper will then move to its Reheat Minimum position.

If check for main fan status has not been selected, the series box fan

will only activate and run when it is in Space Heating mode. When in

Space Heating mode, the damper will move to its Reheat Minimum

position. When in Supply Air Heating mode, the damper will modulate

to maintain the Unoccupied Heating Setpoint.

In all cases, before the series box fan can be activated, the air damper

is driven fully closed and held that way for 30 seconds to make sure

the series box fan hasn’t inadvertently started to spin backwards. Once

the series box fan starts, it waits an additional 10 seconds to allow the

fan to spin up before it starts to open the damper and introduce airflow

from the HVAC unit fan.

Parallel Flow Fan Terminals

If the VAV/Zone Controller has been configured as a Parallel Fan

Powered terminal unit, the Parallel fan will run continuously when the

VAV/Zone Controller is in the Space Heating mode no matter whether

check for main fan status has been selected or not. At all other times,

the fan will be off.

If check for main fan status is selected, the damper will remain in the

closed position until the HVAC unit controller is broadcasting that the

HVAC unit fan is operating, regardless of whether it is calling for heat

or not. The damper will be held at the closed position until the main fan

status broadcast is received. Once the broadcast is received, the damper

will then move to its Night Minimum position. If check for main fan

status has not been selected, the damper will stay in the closed position

until Space Heating mode is initiated. When in Space Heating mode the

damper will move to its Reheat Minimum position. When in Supply Air

Heating mode the damper will modulate to maintain the Unoccupied

Heating setpoint.

Unoccupied Mode Sequences

24

Modular ZCAP Technical Guide

Sequence of Operations