Damper control, Tenant override logs, Damper control and tenant override logs – Orion System Modular VAV/Zone Controller User Manual

Page 25: Sequence of operations, 25 modular zcap technical guide

Advertising
background image

Damper Control and Tenant Override Logs

Damper Control

The damper position is calculated by the mode and demand from the

space sensor. Included in this calculation is an Integral function. This

prevents the damper/airflow from stagnating at a position somewhere

above the setpoint because the supply air temperature or duct pressure

isn’t quite enough to satisfy the space at the currently calculated pro-

portional position. The Integral causes the calculation to keep adding

a small amount of the proportional error back into the damper/airflow

position each time a new position is calculated. The amount the Integral

adds back in is user adjustable. This value is presented as a number

between 0.0 and 10.0. That means that if the integral is less than 1.0,

you are adding a percentage from 0 to 100% of the error back into the

calculation. If you increase the Integral above 1.0, you are adding more

than 100% back in.

With just proportional control, a 1 ºF error would cause a 50% increase

in damper/airflow if the Integral is not included. (1 °F is half of the 2

ºF Proportional Window).

If you had set the Integral to 1.0, the calculation would add 2% to the

current damper/airflow calculation each time. The calculation occurs

once every 10 seconds, so it would take a little over 4 minutes to reach

the programmed 100% maximum.

Example:

1. 50% Remaining / 2% Integral = 25 Moves to get to a 100%

Maximum

2. 25 Moves times 10 seconds = 250 seconds or a little over 4

minutes to reach the 100% maximum damper/airflow

position.

Of course, different space temperature errors and different Integral values

cause this calculation to operate slower or faster. It is up to the user to

determine the optimum setting that provides the tightest temperature

control without causing the damper to continue to hunt or modulate,

causing premature wear of the actuator gears and motor.

On pressure dependent terminal units, the damper position is maintained

to within ± 3% of the calculated position. No attempt is made to position

the damper exactly on the calculated position. This reduces wear and tear

on the actuator gears and motors and the amount of airflow involved is

not affected by that small amount of damper error.

On pressure independent terminal units, the airflow is maintained to

within roughly 3% of the terminal unit size constant but no tighter than

16 CFM on the smallest terminal units. The actual control window is

based on the formula:

Window = Terminal unit size X Square Root (1 / 750)

Where Terminal unit size refers to the total rated CFM of the

terminal unit.

This sliding window allows the control to be much tighter on the smaller

terminal units than can be achieved on the larger terminal units as far as

CFM readings. On a large terminal unit, 25 CFM may not be noticeable,

but on a small terminal unit, 25 CFM may be more than the minimum

airflow setting for the space.

If the pressure sensor is disconnected or fails on a pressure independent

terminal unit, the controller automatically reverts to pressure dependent

operation and generates an alarm to alert the user that a failure has oc-

curred.

On either type of terminal unit, a space sensor failure will force the

damper to position itself to the 50% of the maximum damper position

setpoint, and it will not change until the sensor is repaired or replaced.

Tenant Override Logs

If you require tenant billing for push-button override usage, a MiniLink

Polling Device must be installed on each local loop. The MiniLink Poll-

ing Device has the ability to track the amount of override time generated

by each space sensor equipped with push-button override.

Storing and retrieving these logs requires a dedicated computer run-

ning the Prism front-end software program. No other method exists for

retrieving these logs. That means that all of your units will be connected

together on the communications loop and the loop will be terminated at

a CommLink device connected to an on-site computer.

Warning:

This computer must be on 24 hours a day 7 days a

week running the Prism software in order for tenant

logging to be tracked.

The tenant logs are kept on the dedicated job site computer’s hard drive.

The only limitation to the number of logs stored is the capacity of the

hard drive on the computer to which it is being logged.

Note:

For proper time and date stamping of the tenant log, you

must configure the air handler to broadcast the time so

that the VAV/Zone Controllers can read it and use it in

their tenant and trend logs.

25

Modular ZCAP Technical Guide

Sequence of Operations

Advertising
This manual is related to the following products: