Occupied mode sequences, Sequence of operations, 22 modular zcap technical guide – Orion System Modular VAV/Zone Controller User Manual

Page 22

Advertising
background image

Space Heating Mode

Occupied Space Heating mode is initiated by the temperature in the space

falling to within 0.5 ºF of the Occupied Heating Setpoint.

If the HVAC unit is in the Supply Air Cooling mode and another VAV/

Zone Controller has a heating demand, the damper/airflow for the VAV/

Zone Controller requiring heating will position itself to provide the

Cooling Minimum amount of air into the space. No modulation open

will occur because the space does not want the cold air currently being

supplied by the air handler.

When the HVAC unit is in the Occupied Supply Air Heating mode, the

damper will be held at the Heating Minimum position until the space

temperature falls to within 0.5 ºF of the Occupied Heating Setpoint.

As the space temperature falls below the heating setpoint, the damper/

airflow calculation causes the air valve to open proportionally until the

maximum setpoint is achieved at 1.5 ºF below the setpoint. This is a 2

ºF proportional window starting 0.5 ºF above the heating setpoint to 1.5

ºF below the heating setpoint.

Two different configurations are available for the Occupied Space Heat-

ing mode. If the box is configured to allow reheat during Supply Air

Heating mode, the reheat relays can be activated even when the HVAC

unit is in the Supply Air Heating mode. If the box is configured not to

allow reheat when the HVAC unit is in Supply Air Heating mode, the

box heat relays will be de-energized when the HVAC unit is in Supply

Air Heating mode. In either configuration, when the HVAC unit is in

the Supply Air Heating mode, the damper will modulate open propor-

tionally to the space demand. The proportional window for the space

temperature is to 1.5 ºF below the heating setpoint. This allows the space

to take advantage of the warm supply air in the duct.

The VAV/Zone Controller can activate auxiliary heating relays if the

Expansion Module has been connected and the correct number of heat-

ing stages (1, 2 or 3) has been configured. During demands for heat, the

first stage will activate whenever the space temperature drops below the

heating setpoint. The second stage will activate if the space temperature

falls 1.0 ºF below the heating setpoint. The third stage will activate if

the space temperature falls 2.0 ºF below the heating setpoint. There is a

two-minute delay between staging. This prevents stages from activating

at the same time. Once a heating stage has been activated, it must remain

on for at least one minute. Once it has been deactivated, it must remain

off for at least two minutes. The third stage relay will deactivate when

the space temperature rises to within 1.0 ºF of the heating setpoint. The

second stage relay will deactivate when the space temperature rises to

the heating setpoint. The first stage relay will deactivate when the space

temperature rises above the heating setpoint by 1.0 ºF. See Table 2 for a

complete layout of the various fan & heat relay staging points.

Modulating (Proportional) Heat

The Modular VAV/Zone Controller Actuator Package also provides an

analog output for control of a modulating hot water valve or SCR elec-

tric heater. It provides a 0-10 VDC signal to control the heating device.

When the space temperature drops to 0.5 ºF above the Heating Setpoint

the output starts at 0 VDC and ramps up to 10 VDC at 1.5 below the

Heating Setpoint.

Auxiliary Heat

The Auxiliary Heat option allows for a separate setpoint that is different

from the other heating setpoints. The Auxiliary Heat Relay energizes at

0.5 ºF below the Auxiliary Heat Setpoint and de-energizes 0.5 ºF above

the Auxiliary Heat Setpoint. The Auxiliary Heat will continue to func-

tion regardless of the HVAC Mode the VCM-X is in or at any airflow

condition. This is typically used to control baseboard heat or an external

duct heater. See Table 2 for a complete layout of the various fan and

heat relay staging points.

Fan & Reheat Relay Staging

Relays

Stage On At

Series

Fan

Parallel

Fan

Heat

Stage 1

Heat

Stage 2

Heat

Stage 3

Aux.

Heat

0.5 ºF

Above

Box Heat

Setpoint

ON With

HVAC Fan

*See

Note 1

X

At Box Heat

Setpoint

X

1.0 ºF

Below Box

Heat

Setpoint

X

2.0 ºF

Below Box

Heat

Setpoint

X

0.5 ºF

Below Box

Heat

Setpoint

X

Relays

Stage Off At

Series

Fan

Parallel

Fan

Heat

Stage 1

Heat

Stage

2

Heat

Stage 3

Aux.

Heat

1.0 ºF

Above

Box Heat

Setpoint

OFF With

HVAC Fan

See Note 1

X

See

Note 2

1.0 ºF

Above

Box Heat

Setpoint

X

At Box Heat

Setpoint

X

1.0 ºF

Below

Box Heat

Setpoint

X

0.5 ºF

Above

Aux. Heat

Setpoint

X

Note:

1.) If check for main fan status is selected when configuring the controller, the

series fan will energize anytime the HVAC unit’s fan is operating, even in the

unoccupied mode.

2.) The parallel fan will continue to run for 2 minutes following the relay stag-

ing off.

Table 2: Fan & Reheat Relay Staging

Occupied Mode Sequences

22

Modular ZCAP Technical Guide

Sequence of Operations

Advertising
This manual is related to the following products: