Slaved Zone Damper Wiring

For large zones, it may be necessary to have more than one air damper

controlled by a Modular VAV/Zone Controller Actuator Package and

its associated space sensor. The Orion system allows for connecting

up to two additional slaved zone dampers to the master Modular VAV/

Zone Controller Actuator Package. Slaving is not available for pressure

independent damper applications.

Note:

Each slaved actuator is considered a modular device

rated at 6 VA each. This 6 VA load must be included in

the transformer sizing and branch circuit calculations

for the Power/Comm board. See the previous section

regarding transformer sizing of the Power/Comm board

for complete information.

Two Slave Wiring Adapters (OE267) consisting of a slave wiring inter-

face card and modular cable are supplied with the OE523 Round Slaved

Zone Damper, OE738 Slaved VAV/Zone Rectangular Damper Kit, and

the OE282-03 Slaved VAV/Zone Damper Kit. These are required when

attaching slave actuator(s) to the master zone damper. One slave wiring

interface card should be mounted near the control enclosure of the mas-

ter Modular VAV/Zone Controller Actuator Package. It is mounted by

fastening the plastic snap-track to suitable sheet metal mounting surface

with the sheet metal screws provided. The other card is mounted in the

control enclosure of the slaved zone damper. Run 24 AWG minimum

wire between the slave wiring interface cards. Connect modular cables

to the slave wiring interface cards and to the zone actuators as shown.

See Figure 16 for complete wiring details.

Figure 16: Slaved Zone Damper Wiring & Connection Diagram