Inputs and outputs, Vav/zone controller analog inputs, Other controller connections – Orion System Modular VAV/Zone Controller User Manual

Page 8: Oe325-01 zone controller expansion module, Overview, 8modular zcap technical guide

Advertising
background image

The following inputs and outputs are available on the VAV/Zone

Controller and the OE325-01 Zone Controller Expansion Module. For

component locations of the inputs on the VAV/Zone Controller and VAV

Zone Controller Expansion Module see Figures 3, 4, and 6. For wiring

of inputs and outputs, see Figures 7 through 13.

VAV/Zone Controller Analog Inputs

Space Temperature

The Modular Room Sensor that reads space temperature is attached

to this input. The Modular Sensor connects via a modular cable to the

Modular VAV/Zone Controller Actuator Package.

Airflow Sensor

If the OE744-31-VAVZ Modular VAV/Zone Controller Actuator Package

is being used, the terminal unit’s pressure pick-up tube must be con-

nected with FRP tubing to the barb fittings on the side of the enclosure.

This pressure sensor input is used for CFM (airflow) calculations. If an

Airflow Sensor is attached to this input, the VAV/Zone Controller will

automatically detect this and switch to pressure independent operation.

If the sensor is not attached or becomes defective, the controller auto-

matically reverts to pressure dependent operation.

Supply Air Temperature Sensor

A Supply Air Temperature Sensor can be connected to these terminals. It

should be mounted in the supply duct close to the terminal unit where the

VAV/Zone Controller is installed. This sensor can be used for monitor-

ing purposes or in place of the Supply Air Temperature Broadcast from

the VCM-X Controller.

Other Controller Connections

Expansion Board Modular Connector

This modular connector is used to connect the optional OE325-01 Zone

Controller Expansion Module to the Modular VAV/Zone Controller

Actuator Package. This module is only required when electric or hot

water heating and/or fan terminal control is required. The Expansion

Module is not required for cooling only terminal units.

Actuator Modular Connector

This modular connector is used to connect a modular cable from the

VAV/Zone Controller to a tri-state actuator.

Power/Comm Modular Connectors

These two modular connectors, (labeled P1 & P2), are used to connect

modular cables from the Power/Comm board that supplies 24 Volt power

and communications to the controller and to supply 24 Volt power and

communications from each VAV/Zone Controller Package on the local

loop to the next one on the local loop.

Modular Service Tool DIN Connector

This connector is used to connect a cable between the Modular Service

Tool or the USB-Link and the Modular VAV/Zone Controller Actuator

Package for programing and configuration of the VAV/Zone Controller.

OE325-01 Zone Controller Expansion

Module

As previously stated, when control of a fan or if heating is required, the

OE325-01 Zone Controller Expansion Module is required.

Relay Output #1 - Fan Enable

The first expansion relay on the Output Expansion boards is used for

energizing the fan on Series or Parallel Fan Terminal Units.

Relay Output #2 - Heating Stage 1

If you have at least one stage of heating, this is the relay used to energize

the 1st stage of terminal unit heating. This heating stage can either be

used with electric heat or On/Off hot water valve control.

Relay Output #3 - Heating Stage 2

If you have two stages of electric heating, this relay controls the 2nd

stage of electric heat. For 3 stage heating, this relay output would be

energized for both the 2nd and 3rd stage of heat. See the following

paragraph for more information regarding 3 stage heating applications.

3 Stage Heating Applications

If three stages of electric heat are configured, relays #2 and #3 will stage

in a staggered sequence. This allows you to achieve 3 stages of heating

using only relays #2 and #3. Each of the 3 heating elements should be

sized for one third of the total KW output required. Both the 2nd and 3rd

stage heating contactors (C2 & C3) must be connected to Relay Output

#3. See Table 1 below for relay sequencing information.

Relay Staging

Stage No.

Relay Output #2

Relay Output #3

1

VAV/Zone Controller

Package ON (C1)

OFF (C2 & C3)

2

OFF (C1)

ON (C2 & C3)

3

ON (C1)

ON (C2 & C3)

Table 1: Relay Sequencing For 3 Stage Heating

Auxiliary Heat Relay

If you have an auxiliary heat source you would like to control in addition

to or in lieu of the other heat options, you can connect it to relay R4 on

the expansion module. This relay has a separate setpoint available for

controlling an electric baseboard or duct heater or a two position hot

water valve for a baseboard radiator or duct heater.

Analog Output

If you are using hot water or steam heating via a modulating steam

or hot water valve, this output can supply a 0-10 Volts DC signal for

proportional control of the valve.

Inputs and Outputs

8

Modular ZCAP Technical Guide

Overview

Advertising
This manual is related to the following products: