Unoccupied Mode Sequences

Series Flow Fan Terminals

If the VAV/Zone Controller has been configured as a Series Fan Powered

terminal unit, the series fan relay will activate and run the series box fan

continuously anytime the HVAC unit fan is running.

In all cases, before the series box fan can be activated, the air damper

is driven fully closed and held that way for 30 seconds to make sure

the series box fan hasn’t inadvertently started to spin backwards. Once

the series box fan starts, it waits an additional 10 seconds to allow the

fan to spin up before it starts to open the damper and introduce airflow

from the HVAC unit fan.

Parallel Flow Fan Terminals

On parallel fan powered terminal units, the fan will run whenever Space

Heating mode is active. At all other times, the fan will only activate if the

damper/airflow is below a user defined low limit setting. This causes it

to be used as a make-up air source. When the damper/airflow rises 15%

above the low limit setpoint, the fan will be deactivated if there are no

heating stages active, and no space demand exists.

The check for main fan status setting has no effect on the Parallel Fan

box when in the occupied mode. The Parallel Fan will only be energized

when in the Space Heating mode.

Unoccupied Mode Sequences

Space Vent Mode

This mode only applies to the Occupied Mode of operation. If the

equipment is in the Unoccupied Mode, then a lack of heating or cooling

demand would generate the Off Mode.

Off Mode

This mode only applies to the Unoccupied Mode of operation. If the

equipment is in the Unoccupied Mode, then a lack of heating or cooling

demand would generate this mode. The VAV/Zone Controller will put

the damper into the Night Minimum Position if check main fan status

has been selected. If check main fan status has not been selected, the

damper will be in the fully closed position.

Space Cooling Mode

During unoccupied mode, the HVAC unit is normally off. Unoccupied

Space Cooling mode is initiated by the temperature in the space rising

to within 0.5 ºF of the Unoccupied Cooling Setpoint.

If the HVAC unit is in the Unoccupied Supply Air Heating mode because

one or more of the VAV/Zone Controllers has a heating demand and

another VAV/Zone Controller has a cooling demand, the damper/airflow

for the VAV/Zone Controller requiring cooling will position itself to

provide the heating minimum setpoint amount of air into the space. No

modulation open will occur because the space does not want the warm

air currently being supplied by the air handler.

When the HVAC unit is in the Unoccupied Supply Air Cooling mode,

the damper will be held at the Night Minimum Position until the space

temperature begins to rise above the cooling setpoint. As the space tem-

perature rises to within 0.5 ºF of the Unoccupied Cooling Setpoint, the

damper/airflow calculation causes the air valve to open proportionally

until the maximum setpoint is achieved at 1.5 ºF above the setpoint. This

is a 2 ºF proportional window starting 0.5 ºF below the cooling setpoint

to 1.5 ºF above the cooling setpoint.

The damper/airflow is never allowed to modulate outside the user-

adjusted minimum and the maximum setpoints. The maximum damper/

airflow setpoint applies to heating and cooling modes of operation only.

All of the modes have their own individual minimum setting.

Series Flow Fan Terminals

If the VAV/Zone Controller has been configured as a Series Fan Powered

terminal unit and check for main status has been selected, the series

fan relay will activate and run the series box fan continuously anytime

the HVAC unit fan is running. The damper will be held at the Night

Minimum Position until the space temperature begins to rise above

the cooling setpoint. If check for main fan status has not been selected,

the series fan relay will activate and run the series box fan when in the

Space Cooling mode. The damper will be in the fully closed position

until the space temperature begins to rise above the cooling setpoint.

In all cases, before the series box fan can be activated, the air damper

is driven fully closed and held that way for 30 seconds to make sure

the series box fan hasn’t inadvertently started to spin backwards. Once

the series box fan starts, it waits an additional 10 seconds to allow the

fan to spin up before it starts to open the damper and introduce airflow

from the HVAC unit fan.

Parallel Flow Fan Terminals

In the Unoccupied Cooling mode, the parallel fan will be off whether

check for main fan status has been selected or not. If check for main fan

status has been selected, the damper will be held at the Night Minimum

Position until the space temperature begins to rise above the cooling

setpoint. If check for main fan status has not been selected, the damper

will be held in the fully closed position until the space temperature begins

to rise above the cooling setpoint.

Space Heating Mode

During unoccupied mode, the HVAC unit is normally off. Unoccupied

Space Heating mode is initiated by the temperature in the space falling

to within 0.5 ºF of the Unoccupied Space Heating Setpoint.

If the HVAC unit is in the Unoccupied Supply Air Cooling mode be-

cause one or more of the VAV/Zone Controllers has a cooling demand

and another VAV/Zone Controller has a heating demand, the damper/

airflow for the VAV/Zone Controller requiring heating will position itself

to provide the Night Minimum Position setpoint amount of air into the

space. No modulation open will occur because the space does not want

the cold air currently being supplied by the air handler.

When the HVAC unit is in the Unoccupied Supply Air Heating mode,

the damper will be held at the Night Minimum Position until the space

temperature begins to fall below the Unoccupied Heating Setpoint. As

the space temperature falls to 0.5 ºF below the Unoccupied Heating

Setpoint, the damper/airflow calculation causes the air valve to open

proportionally until the maximum setpoint is achieved at 1.5 ºF below

the setpoint. This is a 2 ºF proportional window starting 0.5 ºF above

the heating setpoint to 1.5 ºF below the heating setpoint.