TROUBLESHOOTING

MHGRV-X Field Technical Guide

14

Alarm Troubleshooting

Supply Air Temperature Failure:

Verify that the Supply Air Temperature Sensor is

connected to the SAT and GND on the MHGRV-X

or MODGAS Controller (stand-alone mode or when

using a CAV/VAV or MUA Controller) or to AI2

and GND on the Main Controller (communicating

mode).

Remove SAT and GND wiring from MHGRV-X

and ohm sensor out (this may indicate open or

failed wiring). Refer to chart in back of this guide

for

readings.

Verify the SAT OPTIONS jumper settings on the

MHGRV-X for the Supply Air Temperature Sensor.

Troubleshooting

MHGRV-X CONTROLLER

(OE377-26-00059)

FAN RELAY LED

ALARM LED

COMPRESSOR RELAY LED
VALVE RELAY LED
AUX RELAY LED

ALARM LED
COMM LED
POWER LED

STATUS LED

CONDENSER DRIVE
LED

REHEAT VALVE DRIVE
LED

REHEAT ENABLE LED

HEAT OVERRIDE LED

COOL OVERRIDE LED

Figure 5: MHGRV-X Controller LED Locations and Descriptions

Communications Loss:

Check COMM LED on MHGRV-X.

Verify 24 VAC power to all interconnected

WattMaster

controllers.

Verify E-BUS connection between the MHGRV-X

and associated WattMaster controllers.

In communication mode (connected to an AAON

Unit

Controller with modular cable), confi rm that

Controller’s MHGRV-X status screen displays

MHGRV-X’s Position % and that Main MHG Reheat

screens show COMM MODE.