Wiring, Mhgrv-x stand-alone wiring, Mhgrv-x field technical guide 6 – Orion System MHGRV-X User Manual

Page 6: Stand-alone wiring, Figure 3: mhgrv-x controller stand-alone wiring

Advertising
background image

WIRING

MHGRV-X Field Technical Guide

6

MHGRV-X Stand-Alone Wiring

Figure 3: MHGRV-X Controller Stand-Alone Wiring

Line

GND

24V

AC

40 VA

Transformer

Minimum

Supply

Air Temperature

Sensor

Mount In Supply

Air Duct

RED

GRN

WHT

BLK

Condenser Valve #1

HGR Valve #1

RED

GRN

WHT

BLK

MHGRV-X CONTROLLER

(OE377-26-00059)

Fan

Compressor

HGR Solenoid Valve

2 Position HGR Valve (Optional)

C1

C2

COMM

-

+

0-10VDC

External Reset

Signal

Heating Override

H1 (Dehumidification)

Cooling Override

See

For SAT OPTIONS Jumper Settings.

Only One Supply Air Temperature

Sensor Can Be Used Per Application.

Table 8 On Page 18

EBC E-BUS

Cable Connects

To Reheat

Expansion

Module

Stand-Alone Wiring

In Stand-Alone mode, the MHGRV-X connects to the E-BUS port
of the Reheat Expansion Module with an EBC E-BUS cable.

See the SAT Wiring Conditions Table and SAT OPTIONS jumper
settings in Tables 7 & 8, page 18.

See Figure 3 below.