Appendix a, Sat sensor wiring guide & jumper settings, Sat wiring conditions – Orion System MHGRV-X User Manual

Page 18

Advertising
background image

APPENDIX A

MHGRV-X Field Technical Guide

18

SAT Options Jumper Settings

Refer to Tables 8 & 9 to determine the SAT Option Jumper settings.
See Figures 2 & 3 on pages 5 & 6 for jumper locations.

STAND-ALONE MODE

SAT OPTIONS JUMPER SETTINGS*

CONDITION

SETTING

MHGRV-X Only

Normal

MHGRV-X with

MODGAS-X**

MODGAS-X

MHGRV-X with

MODGAS II***

MODGAS

* For SAT Sensor testing, use Table 7 for
Normal & MODGAS-X jumper setting and use
Table 8 for MODGAS jumper setting.

** In this situation, also set MODGAS-X SAT
Option to Jumper Setting 1. See the MODGAS-X
Technical Guide
for more information.

*** The MODGAS II must have PU1 resistor
installed.

Table 8: Stand Alone Mode SAT OPTIONS Jumper
Settings

COMMUNICATIONS MODE

SAT OPTIONS JUMPER SETTINGS*

CONDITION

SETTING

VCM / VCM-X / SA/ RNE *

Normal

MUA, VAV/CAV**

Normal

VCB-X*

Normal

* For SAT Sensor testing, use Table 7 for Normal
jumper setting. SAT should be connected to the
Main Controller.

** For SAT Sensor testing, use Table 7 for Normal
jumper setting. SAT should be connected to the
MHGRV-X Controller.

Table 9: Communications Mode SAT OPTIONS
Jumper Settings

SAT Wiring Conditions

MODGAS-X ONLY

MHGRV-X ONLY

MODGAS-X & MHGRV-X

STAND-

ALONE

Install Supply Air
Sensor in MODGAS-X.

Install Supply Air
Sensor in MHGRV-X.
Set “SAT Options”
Jumpers to “Normal”.

Install Sensor in MODGAS-X and daisy-chain it
to the MHGRV-X. Set “SAT Options” Jumpers to
“MODGAS X”. If connected to a MODGAS II
Retrofi t, Set “SAT Options” Jumpers to “MODGAS”.

VCB-X

Install Supply Air Sensor
in VCB-X.
Connect to VCB-X
using E-BUS cable.

Install Supply Air
Sensor in VCB-X.
Connect to VCB-X
using E-BUS cable.

Install Supply Air Sensor in VCB-X.
Connect to VCB-X using E-BUS cable.

VCM-X,

SA, RNE

Install Supply Air Sensor
in Main Controller.
Connect to Main
Controller using I

2

C

cable.

Install Supply Air
Sensor in Main Controller.
Connect to Main
Controller using I

2

C cable.

Install Supply Air Sensor in Main Controller.
Connect to Main Controller using I

2

C cable.

VCM,

VAV/CAV,

MUA,

MUA II,

MUA IID

Install Supply Air Sensor
in MODGAS-X.
Connect to Main
Controller using I

2

C

cable.

Install Supply Air
Sensor in MHGRV-X.
Connect to Main
Controller using I

2

C cable.

Install Supply Air Sensor in MODGAS-X.
Connect to Main Controller using I

2

C cable.

Table 7: SAT Wiring Conditions

SAT Sensor Wiring Guide & Jumper Settings