APPENDIX C - REHEAT EXPANSION MODULE

MHGRV-X Field Technical Guide

24

LED Diagnostics

The Reheat Expansion Module is equipped with 4 LEDs that can be
used to verify operation and perform troubleshooting.

See Figure 10 below for the LED locations. The LEDs associated
with these inputs and outputs allow you to see what is active without
using a voltmeter. The LEDs and their uses are as follows:

Operation LEDs

POWER

- This green LED will light up to indicate that 24 VAC

power has been applied to the Expansion Module.

STATUS

- This green LED will light up and blink every 10 seconds

according to valve position. One blink per 10%. Example: valve
position is 67%. STATUS LED will blink 6 times every 10 second
cycle. The STATUS LED will stay on solid during the 2 minute fl ush
cycle. See Table 10 below.

No. of

Blinks

STATUS LED

1 - 10

Per 10% Valve Position

SOLID

During 2 Minute Flush Cycle

Table 10: STATUS LED Blink Codes

LED Diagnostics & Troubleshooting

Communication LED

COMM

- This amber LED will light up and blink once for every

good packet received. Packets should be sent once every second,
so Comm LED should blink the same, once every second. COMM
LED should blink simultaneously on all modules.

Binary Input LED

COMPRESSOR ENABLE

- This green LED will light up when

the Reheat is enabled.

LED Troubleshooting

“POWER” LED: When the Reheat Expansion Module is powered up,
the POWER LED should light up and stay on continuously. If it does
not light up, check to be sure that the power wiring is connected to the
board, the connections are tight, and the transformer is powered. If after
making all these checks, the POWER LED does not light up, the board
is probably defective.

“STAT” LED:

When the board is fi rst powered up, the STAT LED

will do the following:



On for 10 seconds



Blinks 30 times



Status code is repeatedly blinked every ten seconds to

indicate valve position

Figure 10: Reheat Expansion Module(s) Wiring

24VAC

GND

COM

M

GND

ENABL

E

BLACK

WHITE

RED/GRN

GRN/RED

COND/REHEAT

YS102608 R0

WATTMASTER
CONTROLS INC

2013

COMM

STATUS

COMM LED

POWER
LED

STATUS LED

COMM

STATUS

COMPRESSOR
ENABLE
LED