APPENDIX C - REHEAT EXPANSION MODULE

21

General Wiring Information

For the wiring diagram to use when the MHGRV-X Controller is
connected to an AAON Unit Controller, see Figure 2, page 5. For
the stand-alone wiring diagram, see Figure 3, page 6.

For Reheat Expansion Board wiring, see Figure 9, page 22.

Please carefully read and apply the following information when
wiring the Reheat Expansion Module(s):

1.

18 gauge minimum wire unless otherwise noted.

2.

24 VAC power connection with an appropriate VA rating.

3. Compressor Enable must have 24 gauge minimum wire.

4. All 24 VAC wiring must be connected so that all ground

wires remain common. Failure to follow this procedure can
result in damage to the module and connected devices.

5. All wiring is to be in accordance with local and

national electrical codes and specifi cations.

6. Check all wiring leads at the terminal block for tightness.

Be sure that wire strands do not stick out and touch
adjacent terminals. Confi rm that all transducers required for
your system are mounted in the appropriate location and
wired into the correct terminals.

Installation & Wiring

Installation & Mounting

The Reheat Expansion Module is provided with a Chevron cut
plastic snap track mounting base. The snap track is designed to be
mounted using a ¼” Hex Head Sheet Metal Screw (provided) to a
fl at surface using the pre-punched mounting hole that is provided
in the center of the snap track. The Reheat Expansion Module is
then snapped into place on the snap track, providing for easy fi eld
mounting and servicing.

The Reheat Expansion Module needs to be installed in an envi-
ronment which can maintain a temperature range between -30°F
and 150°F not to exceed 90% RH levels (Non-Condensing). It is
important to keep the module in a location that is free from extreme
high or low temperatures, moisture, dust, and dirt. Be careful not to
damage the electronic components.

NOTE: The Reheat Expansion Module contain no user-

serviceable parts. Contact qualified technical
personnel if your Controller or Module is not operat-
ing correctly.