1 important notes prior to installation, 2 wall openings, 3 installation materials – REMKO RVT 263 DC User Manual

Page 27: 4 installation indoor unit, 5installation instructions for qualified personnel

Advertising
background image

5

Installation instructions for qualified personnel

5.1 Important notes prior to instal-

lation

n

Transport the unit in its original packaging as

close as possible to the installation location.

You avoid transport damage by doing so.

n

Check the contents of the packaging for com-

pleteness and check the unit for visible trans-

port damage. Report any damage immediately

to your contractual partner and the shipping

company.

n

Lift the unit on the corners and not on the

refrigerant or condensate drainage connec-

tions.

n

The refrigerant piping (liquid and suction pipe),

valves and connections must be insulated to

make them vapour diffusion proof. If necessary

also insulate the condensate drainage line.

n

Select an installation location which allows air

to freely flow through the air inlet and outlet

(see section "Minimum clearances")

n

Do not install the unit in the immediate vicinity

of devices which generate intensive thermal

radiation. Installation in the vicinity of thermal

radiation reduces the unit output.

n

Only open the shut-off valves on the refrigerant

piping after installation is complete.

n

Seal off open refrigerant piping with suitable

caps or adhesive strips to prevent the infiltra-

tion of moisture and never kink or compress

the refrigerant piping.

n

Avoid unnecessary bends. This minimises the

pressure loss in the refrigerant piping and

ensures that the compressor oil can flow back

without obstruction.

n

Make special preparations regarding the oil

return if the outdoor unit is located above the

indoor unit (see section "Oil return measures").

n

Add refrigerant if the basic length of the refrig-

erant piping exceeds 5 metres. For the quantity

of additional refrigerant, refer to chapter

"Adding refrigerant".

n

Perform all electrical wiring in accordance with

applicable DIN and VDE standards.

n

Ensure the electrical cables are properly con-

nected to the terminals, otherwise there is a

risk of fire.

n

Only use the fasteners contained in the scope

of delivery with the units.

n

Use four supports and the associated hooks to

attach the ceiling cassette (only applies to

ceiling cassettes).

n

Use the insulated condensate hose in the

scope of delivery as a junction piece to the

continuing condensate drain. Secure the con-

densate drain with the supplied clamps.

5.2 Wall openings

n

A wall opening of at least 70mm diameter and

10mm incline from the inside to the outside

must be created.

n

To prevent damage to the lines, the interior of

the wall opening should be padded or, for

example, lined with PVC pipe (see figure).

n

After installation has been completed, use a

suitable sealing compound to close off the wall

opening, taking account of fire protection regu-

lations (responsibility of customer). Do not use

cement or lime containing substances!

2

1

5

3

4

Fig. 30: Wall opening

1: Liquid line

2: Control line

3: Condensate drainage line

4: Suction pipe

5: PVC pipe

5.3 Installation materials

The indoor unit is attached to the wall by a wall

bracket and 4 screws (to be provided by the cus-

tomer).

The outdoor unit is attached by 4 screws and a

wall bracket to the wall or fixed by a floor bracket to

the ground.

5.4 Installation indoor unit

The indoor unit is designed for horizontal wall

installation above doors. However, it can also be

used in the upper wall area (min. 1.75m above the

floor).

27

Advertising
This manual is related to the following products: