6 installation, 1 installation of the indoor unit, 2 connecting the refrigerant piping – REMKO RVT 263 DC User Manual

Page 33: 6installation

Advertising
background image

6

Installation

6.1 Installation of the indoor unit

The indoor unit is attached by means of a wall

bracket, taking into consideration the air outlet side

located in the lower part.

1.

Mark the mounting points on the structurally

permissible building sections according to the

dimensions of the wall bracket.

2.

If necessary, remove the break out opening

of the housing.

3.

Connect the refrigerant piping, electrical

cables and condensate drainage line to the

indoor unit as described below.

4.

Hang the indoor unit onto the wall bracket by

tilting it back slightly and by pressing the

bottom part of the unit against the bracket.

5.

Check again that the unit is level. (Fig. 38)

Fig. 38: Horizontal positioning

The wall bracket for the units must be attached

with suitable screws and anchors.

6.2 Connecting the refrigerant

piping

The refrigerant piping is connected (responsibility

of the customer) on the back side of the units.

It may be necessary to fit a reducer or flared

adapter to the indoor unit. These fittings are

included with the indoor unit as an accessory kit.

Once installed, the connections should be insu-

lated to make them vapour diffusion proof.

NOTICE!

Installation should only be performed by

authorised specialists.

NOTICE!

The unit is factory filled with dry nitrogen for

leak testing purposes. The pressurised

nitrogen is released when the union nuts are

undone.

NOTICE!

Use only tools which are approved for use in

an HVAC environment. (z. B.: bending pliers,

pipe/tubing cutters, de-burrers and flaring

tools). Do not cut refrigerant pipes with a saw.

NOTICE!

All work must be carried out in a way that pre-

vents dirt, particles, water etc. from entering,

refrigerant lines!

33

Advertising
This manual is related to the following products: