7 condensate connection and safe drainage, Condensate connection and safe drainage, 7condensate connection and safe drainage – REMKO RVT 263 DC User Manual

Page 37

Advertising
background image

7

Condensate connection

and safe drainage

3

2

4

9

5

5

11

100

6

8

7

10

10

12

12

1

Fig. 43: Condensate drainage, seepage of conden-

sate and strip foundation (cross-section)

1:

Outdoor unit

2:

Leg

3:

Condensate collection tray

4:

Floor bracket

5:

Reinforced strip foundation

HxWxD = 300x200x800mm

6:

Gravel layer for seepage

7:

Condensate drainage heating

8:

Drainage channel

9:

Conduit for refrigerant piping and electrical

connecting line (temperature-resistant up to at

least 60°C)

10: Frost line

11: Drainage pipe

12: Soil

E

B

B

A D

C

11

1

5

5

8

1

9

3

Fig. 44: Dimensions for the strip foundation (bird's

eye view)

Please see the legend of Fig. 43 for the descrip-

tions of 1,3,5,8,9 and 11

Dimensions of the strip foundation (in mm)

Dimen-

sion

RVT 263 DC-523

DC

RVT 683 DC

A

800

800

B

200

200

C

530

590

D

290

333

E

330

390

Condensate drainage connection

If the temperature falls below the dew point, con-

densation will form on the finned condenser during

heating mode.

A condensate tray should be installed on the

underside of the unit to drain any condensate.

n

The condensate tray should have an incline of

min. 2%. This is the responsibility of the cus-

tomer. If necessary, fit vapour-diffusion-proof

insulation.

n

When operating the unit at outside tempera-

tures below 4

℃, ensure the condensate

drainage is laid to protect it against frost. The

lower part of the housing and condensate tray

is also to be kept frost free in order to ensure

permanent draining of the condensate. If nec-

essary, fit a pipe heater.

n

Following installation, check that the conden-

sate run off is unobstructed and ensure that the

line is durably leak tight.

37