Error EC: Refrigerant leakage detection

Shut off the power supply and turn it on 5 sec-

onds later. Is it still displaying the error code?

YES

Is there cool air blowing out from indoor air

outlet?

YES

Check if T2 sensor is well fixed. Correct the

installation or replace T2 sensor. Does the

problem remain again?

NO

YES

Is there any leakage? Especially the connec-

tions parts, such as the gas valve and the liquid

valve.

Replace indoor PCB.

YES

Repair the leakage and recharge the refrig-

erant.

NO

Is there any blocking? (such as the capillary or

the welded points of the pipes).

YES

Clear the blocking.