Error P0: IPM malfunction or IGBT over strong current protection

Check if the wiring between module PCB and

compressor connected correctly.

NO

Correct the connection.

YES

IPM continuity check. Check if the IPM terminal

resistance values are uniform.

NO

Replace the module PCB.

YES

Check if the IPM installed correctly. Check if the

outdoor fan can run properly

NO

Correct the installation, tighten the screws and

apply silicon grease. Correct the connection of

fan motor or reolace the fan motor.

YES

Replace outdoor control PCB. Does the

problem still remain?

YES

Replace the compressor.

Error P1: Over voltage or over low voltage protection

Check if the power supply is normal.

NO

Disconnect the unit with power supply and try to

restart the unit when power supply gets normal.

YES

Check if all the connections are good

NO

Correct the connections.

YES

Check if the voltage between P and N is around

DC 320V

YES

Replace outdoor control PCB.