Error E1: Indoor/outdoor units communication error

Power off, then turn on the unit 5 seconds later

(reconnect the power wire). Is the erorr still dis-

playing after several minutes?

YES

Check all the wirings between indoor and out-

door, indoor PCB and outdoor PCB following

the wiring diagram. Are all the wirings con-

nected correctly?

YES

Is -24V<Vs<+24V?

(Vs is the voltage between S and N of outdoor

unit).

NO

Is the wiring to the indoor PCB connected cor-

rectly?

YES

YES

Is the wiring to the outdoor PCB connected cor-

rectly?

Change the indoor PCB.

YES

Change the outdoor main PCB.

NO

Power on. Is the error extinguished?

Error E2: Zero crossing detection error

Check if the connections and power supply is

normal?

NO

Correct the connections. Turn on the unit when

the power supply is good.

YES

Indoor PCB is defective. Replace indoor PCB.