Remko rm, Technical data – REMKO RM Series User Manual

Page 34

Advertising
background image

REMKO RM

34

Technical data

Series

RM 226

RM 235

RM 252

RM 268

Operating mode

Multisplit wall-mounted air-conditioning combinations for cooling

Nominal cooling output

1)

kW

2 x 2.62

2 x 3.56

2 x 5.25

2 x 6.89

Energy efficiency class, cooling

1)

B

C

C

B

Energy efficiency ratio EER

1)

3,06

2,87

2,88

3,02

Operating range (room volume), approx.

2 x 80

2 x 110

2 x 160

2 x 230

Refrigerant

R 410A

Voltage supply

V/Hz

230 / 1~ / 50

Nom. electrical power consumption, cooling

1)

kW

1,71

2,48

3,64

4,56

Nom. current consumption, cooling

1)

A

7,50

11,40

16,30

21,10

Electr. starting current, max.

A

2 x 21

2 x 28

2 x 36

2 x 51

Refrigerant connection, injection pipe

Inches

(mm)

1/4

3/8

Refrigerant connection, suction pipe

Inches

(mm)

3/8

1/2

5/8

Max. operating pressure

kPa

4200 / 4200

Data specific to

indoor unit

RM 226 IT

RM 235 IT

RM 252 IT

RM 268 IT

Adjustment range, room temperature

°C

+16 to +31

Working range

°C

+15 to +31

Air flow rate per stage

m³/h

320/370/420

380/450/520

600/700/800

800/900/1000

Noise output per stage

3)

dB(A)

30/34/38

32/36/40

35/39/43

37/41/45

Protection degree

IP

X0

Condensation connection

mm

17

17

17

17

Dimensions Height

mm

275

275

275

320

Width

mm

790

790

930

1035

Depth

mm

200

200

200

220

Weight

kg

8.0

10.0

12.0

16.0

Data specific to

outdoor unit

RM 226 AT

RM 235 AT

RM 252 AT

RM 268 AT

Working range, cooling

°C

+7 to +48

Air flow rate, max.

m³/h

2310

4455

5665

Protection degree

IP

24

Noise level, max.

3)

dB(A)

50

52

54

57

Refrigerant, basic quantity

kg

2 x 0.85

2 x 1.00

2 x 1.45

2 x 1.80

Refrigerant, additional quantity> 5 m

g/m

25

45

Refrigerant pipe, max. length

m

25

Refrigerant pipe, max. height

m

15

Dimensions Height

mm

615

1240

Width

mm

845

830

930

Depth

mm

285

310

390

Weight

kg

52

56

115

125

Serial number

845...

846...

847...

848...

Computerised part no.

1630226

1630235

1630252

1630268

1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air flow rate
2) Air inlet temperature TK 20°C, outdoor temperature TK 7°C / FK 6°C, max. air flow rate
3) Distance 1 m free air

Advertising