Remko system monitor, For remko supertec inverter – REMKO SuperTec-Monitor User Manual

Page 16

Advertising
background image

Setting on SW2

System component

Measuring range and description

Unit

DC bus voltage

CMF 80/90/140/150

CMT 100/150

180 - 370

180 – 370

If the voltage is over 99 V, the

display switches

between the 100s digit1

and the 10s and 1s digits.

°C

ON

1 2 3 4 5 6

Fan speed before fault

0 – 10

0 – 10

Levels /

Steps

ON

1 2 3 4 5 6

Fault on the temperature sen-

sor

If no temperature sensor fault

has occurred,

"—" appears on the

LED display.

3 = Liquid line on the

outdoor unit TH3, TH32

6 = two-phase line

(condenser/vaporiser)

on the outdoor unit TH6

7 = Outdoor air temperature

TH7

8 = Cooling fin temperature

sensor TH8

Code

ON

1 2 3 4 5 6

Condenser operating frequency

before fault

0 – 255

0 – 255

If the operating frequency is

over 99 H�, the display

switches between the 100s

digit, the 10s and 1s digits,

and 2 spaces.

Example: 125 H�:

H�

ON

1 2 3 4 5 6

0.5 s

0.5 s

2 s

„ 1“ „25“ „ “

REMKO SYSTEM MONITOR

FOR REMKO SUPERTEC INVERTER

16