Remko system monitor, For remko supertec inverter – REMKO SuperTec-Monitor User Manual

Page 8

Advertising
background image

If the condenser is switched off by
a protective device after a fault
has occurred, the LED display al-
ternates between showing the unit
address of the air conditioner in
question and the fault code.

LED display flashes when a fault
has occurred

Interval:

1 second

Address of the

malfunctioning

air conditioner

Fault code

Display

Description (during operation)

U1

Fault on the high pressure switch, 63H was triggered

U2

Hot gas temperature too high, lack of refrigerant

U3

Hot gas temperature sensor TH 4 detected open circuit /short-circuit

U4

Temperature sensor TH3, TH6, TH7, TH8 in outdoor unit detected open circuit/short-circuit

U5

Cooling fin temperature sensor detected open circuit/short-circuit

U6

Fault in the power module (inverter)

U7

Overheating fault; hot gas temperature too low

UF

Condenser stopped due to overcurrent (condenser disabled)

UH

Fault on the current sensor

UL

Fault on the low pressure switch, 62L was triggered

UP

Condenser stopped by overcurrent

A0-A7

Data transmission fault: priority signal on the M-net

Display

Description (during operation)

F3

Connector 63L (red) is disconnected

F5

Connector 63H (yellow) is disconnected

F9

Both connector 63L and 63H are disconnected

E8

Data transmission fault: outdoor unit is not receiving any signals from the indoor unit

E9

Data transmission fault: outdoor unit is not transmitting any signals to the indoor unit

EA

Wiring fault in the interior/exterior control cables: too many indoor units (max. 4)

Eb

Wiring fault in the interior/exterior control cables: polarity reversed, cable detached

Ec

Timeout on system startup

E0-E7

Data transmission fault: other without outdoor unit