Fault codes

When a fault occurs, the fault
code is issued on the outdoor
unit using flashing codes on
two LEDs

!

CAUTION

Please note the following when a fault message is issued:

In the event of a communication error, the information from the LED
indicators of the outdoor unit and that on the display of the REMKO
SYSTEM MONITOR may differ, or the outdoor unit may not show a fault
at all.
If a fault occurs, you can determine its cause from the following tables.

Fault code display

Description

LED 1 (green)

LED 2 (red)

Display

Flashes once

Flashes
once

F1

Phase fault detected
Phase fault, wiring fault between indoor/outdoor unit

F2

Phase fault detected
Open L3-phase detected

Flashes
twice

F3

Connector 63L open
No contact detected from 63L for 3 min.

F4

Connector 49C open
No contact detected from 49C for 3 min.

F5

Connector 63H open
No contact detected from 63H for 3 min.

F9

Two or more connectors open
At least two open connector contacts detected

Flashes 3
times

FA

L2-phase or connector 51CM open
No L2-phase or no contact detected from 51CM for 3 min.

F7

Fault on the phase fault detection circuit (control board)
No signal detected on control board

F8

Fault with the system circuitry
No feedback signal received from the indoor unit 0.5 sec. after applying the supply
voltage

Flashes twice

Flashes
once

EA

Wiring fault between indoor and outdoor unit

Eb

Wiring fault between indoor and outdoor unit
(cable break, loose connection)

Flashes
twice

E8

Data transfer between indoor and outdoor unit

E9

Flashes 4
times

Fb

Fault on the control board in the indoor unit

REMKO SYSTEM MONITOR

FOR REMKO SUPERTEC INVERTER

20