Fault code display

Description

LED 1 (green)

LED 2 (red)

Display

Flashes 3 times

Flashes
once

U2

Hot gas temperature sensor
Internal thermostat of compressor motor 49C was triggered.
Refrigerant level

U7

Hot gas overheating too low

Flashes
twice

U1

High pressure switch 63H was triggered

UE

UL

Low pressure switch 63L was triggered

Flashes 3
times

Ud

Overheating protection function

Flashes 4
times

U6

Circuit breaker on the condenser (overload)

Fault in the power module

UA

Circuit breaker on the condenser (thermal overload relay)

Thermal overload relay is triggered
Only for models with a three-phase power supply

UC

Condenser switched off by internal protection function

UF

Condenser blocked, overcurrent protection device was triggered

UP

Overload protection device was triggered

UH

Fault on the current sensor

Flashes 5
times

U3

Fault on the hot gas temperature sensor TH4

U4

Fault on the line temperature sensor of the outdoor unit TH3

Fault on the heat exchanger temperature sensor of the outdoor unit TH6

Fault on the outdoor air temperature sensor of the outdoor unit TH7

Fault on the inverter cooling block temperature sensor TH8

Flashes 6
times

U5

Temperature fault on inverter cooling block

Flashes 7
times

U6

Fault in power supply

21