2 connecting the cables for the supply voltage, Connecting the cables for the supply voltage – SMA External Supply Voltage 230 V User Manual

Page 137

Advertising
background image

Procedure:

1. Disconnect the inverter on the DC side (see inverter manual).
2. Disconnect the SMA String-Monitor (see SMA String-Monitor manual).
3. Disassemble the lower protective cover of the SMA String-Monitor (see SMA String-Monitor

manual).

4. Push the connectors of the power supply assembly onto the connectors of the electronic

assembly in the SMA String-Monitor.

5. Screw the spacer bolts supplied in the scope of delivery through the holes of the power supply

assembly onto the mounting pins. As a result, the power supply assembly is fused.

6. Connect the cables for the supply voltage (섹션 참조 섹션 참조 4.4.2, 페이지의 137).

4.4.2

Connecting the Cables for the Supply Voltage

Requirements:

☐ The SMA String-Monitor must be disconnected (see SMA String-Monitor manual).
☐ The inverter must be disconnected on the DC side (see inverter manual).
☐ The power supply assembly must be installed (섹션 참조 섹션 참조 4.4.1, 페이지의 136).

Cable requirements:

☐ Conductor cross-section: 1.5 mm

2

to 2.5 mm

2

☐ Recommended cable type: NYY-O
☐ If large distances and small cable cross-sections are involved, take the voltage drop into

account.

Procedure:

1. Remove the sealing plugs from the corresponding enclosure openings (섹션 참조 섹션 참

조 4.2, 페이지의 134).

2. Lead the cables for the supply voltages through the enclosure openings into the SMA String-

Monitor.

3. Dismantle the cables by 80 mm.
4. Strip off the insulation of each conductor by 12 mm. Make sure that no pieces of cable are

dropped into the SMA String-Monitor.

5. Connect the cable for incoming supply voltage

to terminals X22:2,3. To do this, insert the cable
into the terminal and close the locking lever of
the terminal.

4 설치

SMA Solar Technology AG

Installation Manual

137

SSMU-AUX-PB/OVP-IA-xx-10

한국어