6. Connect the cable for outgoing supply voltage to terminals X21:1,2. To do this, insert the

cable into the terminal and close the locking lever of the terminal.

7. Make sure that the cables are securely in place.
8. Tighten the swivel nut of the cable gland (torque: 4 Nm).
9. Ground the power supply assembly (섹션 참조 섹션 참조 4.4.3, 페이지의 138).

4.4.3

Grounding the Power Supply Assembly

The parts to be grounded can be connected to a joint grounding electrode.

Requirements:

☐ The SMA String-Monitor must be disconnected (see SMA String-Monitor manual).
☐ The inverter must be disconnected on the DC side (see inverter manual).
☐ The external supply voltage of the SMA String-Monitor must be disconnected (see manual of

the inverter or manual of the external voltage source).

☐ The power supply assembly must be installed (섹션 참조 섹션 참조 4.4.1, 페이지의 136).
The supply voltage cables must be connected (섹션 참조 섹션 참조 4.4.2, 페이지의 137).

Cable requirements:

☐ Conductor cross-section: 6 mm

2

☐ Recommended cable type: NYY-O

Procedure:

1. Remove the sealing plug from the enclosure opening for the external functional grounding of

the power supply assembly (섹션 참조 섹션 참조 4.2, 페이지의 134).

2. Lead the grounding cable through the enclosure opening into the SMA String-Monitor.
3. Dismantle the grounding cable by 12 mm. Make sure that no pieces of cable are dropped

into the SMA String-Monitor.

4. Connect the grounding cable to the terminal

X22:1 for functional grounding. To do this, insert
the cable into the terminal and close the locking
lever of the terminal.

5. Ensure that the grounding cable is securely in place.
6. Tighten the swivel nut of the cable gland (torque: 2.5 Nm).
7. Ground the grounding cable in the vicinity of the SMA String-Monitor, e.g. by means of a

grounding electrode.

8. Replace the lower protective cover of the SMA String-Monitor (see SMA String-Monitor

manual).