Maintaining the Sunny String-Monitor-Cabinet

SMA Solar Technology AG

60

SCWAR-WEN094020

Maintenance Manual

9. Check all power cable connections for looseness and tighten them if necessary. Check the

connectors and insulation for discoloration or degradation. Replace any damaged connectors
or corroded contacts.

10. Check all string cable connections for looseness and tighten them if necessary. Check the

insulation, and the terminals on the assembly as well on the busbar for discoloration or
degradation.

11. Check all cable connections of the optional DC main switch for looseness and tighten them if

necessary. Check the insulation and the switch for discoloration or degradation.

12. Check the shield connection of the communication cables. The shield connection must only be

hand-tightened.

13. Check the ground connection and the contact resistance to the ground potential.
14. Check the overvoltage protector. The visual display must be green.
15. Check the filter pads of the ventilation grids for dirt and clean or replace them, if necessary.

Replacement filter pads can be ordered from SMA Solar Technology AG.

☑ Maintenance of the Sunny String-Monitor-Cabinet is completed.