Maintaining the Sunny Central

SMA Solar Technology AG

12

SCWAR-WEN094020

Maintenance Manual

Cleaning the filter pads

• Clean with water (up to approx. 40 °C; you can also additionally use commercially available

mild detergent).

• Tap or vacuum the filter material, or carefully use pressurized air to remove the contamination.
• For dust containing grease, you should rinse with warm water and additionally use degreaser.

The air filter pad may not be cleaned with strong water jet or wrung out.

• As soon as the air filter pads are cleaned and dried, put them back into the frame.

Cleaning the ventilation grids

• The grids can be cleaned using a paintbrush, vacuum, or applying pressurized air.

3.4.2 Sunny Central 100LV / SC 150 / SC 125LV / SC 200 / 200HE

Position of the ventilation grids
With the help of some example cabinets, the following section shows the exact position
and size of the individual ventilation grids.

The switch cabinets of type SC 100LV, SC 150,
SC 125 LV and SC 200 are mostly identical in
construction and equipped with four large air inlet filters
(A).