2 Product Overview

2

Product Overview

About this Product

The 24 V Power Supply Option maintains unit control circuit power in the event of a main

power outage. As long as the control circuit has power, network communications and I/O

data remain operational. The option provides external power to the control circuit only, and

does not provide power to the main circuit of the unit.
It is possible to read fault and parameter data in the unit via the operator or network

communications when the unit switches to the option as a back-up power supply.

Note: 1. Parameter settings cannot be changed without unit main circuit power regardless of whether the control

circuit has enough power to operate.

2. When connecting the Option, set the unit Undervoltage Detection Level (Uv) to its default value.

Applicable Models

The Option can be used with the unit models in

Table 1

.

Table 1 Applicable Models

Unit

Option Model

A1000

CIMR-A†2A††††

PS-A10LB

CIMR-A†4A††††

PS-A10HB

CIMR-A†5A††††

L1000A

CIMR-L†2A††††

PS-A10LB

CIMR-L†4A††††

PS-A10HB

CIMR-L†5A††††

T1000A

CIMR-T†2A††††

PS-A10LB

CIMR-T†4A††††

PS-A10HB

Z1000

CIMR-Z†2A††††

PS-A10LB

CIMR-Z†4A††††

PS-A10HB

D1000

CIMR-D†2A††††

PS-A10LB

CIMR-D†4A††††

PS-A10HB

R1000

CIMR-R†2A††††

PS-A10LB

CIMR-R†4A††††

PS-A10HB