YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure

Z1000U Bypass
Quick Start Procedure

Page 12

of 37

The HAND and AUTO frequency references can be set independently.

The factory default for HAND frequency reference originates from the HOA keypad.

The factory default for AUTO frequency reference originates from drive analog inputs A1 or A2.

7.1 Ensure the HOA keypad cable is fi rmly connected between the HOA keypad door mounted

cable port and communications port CN2 on the bypass controller board.

7.2 Energize the Bypass.

HOA Keypad Tutorial (continued)

6

STEP

Confi gure the HAND and AUTO Frequency Reference

7

STEP

Display

FUNCTION KEY 1 (F1)

HELP

Press F1 to display the Help menu.

<--

Press F1 to scroll the cursor to the left.

HOME

Press F1 to return to the top menu
(Frequency Reference).

ESC

Press F1 to return to the previous
display.

RLY

Press F1 to select/deselect Drive Test
Mode. During Drive Test Mode, power
is applied to the drive while in Bypass
Mode by forcing the drive input contac-
tor to close (3-contactor bypass only).

Freq Ref (AUTO)

Display

BYPASS STATUS DISPLAY

AUTO XFER EN Running in Auto Transfer,

a fault was detected and
switched to Bypass Mode.

ENRGY SAVE EN Running in Energy Savings

Mode

MTR STOPPING Fault is removed but motor is

still ramping down.

FAULTED

Fault has been detected caus-
ing motor output contactors
to open.

Display

BYPASS STATUS DISPLAY

POWERUP

Bypass is powering up.

OFF

No Run command is present and
the safety circuit is closed.

WAIT FOR RUN

AUTO mode:
-Safety circuit is closed
-Bypass waits for Run input.

SAFETY OPEN

The safety circuit input is open.

INTRLOCK OPN

Run command is present, the
safety circuit is closed, but the
Interlock input is open.

PRE RUN DRIVE

Bypass is running in the Pre-Run
State at the programmed fre-
quency for the programmed time.

RUN DRIVE

Running in Drive Mode.

RUN BYPASS

Running in Bypass Mode.

RMOT XFER EN

Running in Remote Transfer.

SMOK PRG BYP

Running in Smoke Purge Bypass.

SMOK PRG DRV

Running in Smoke Purge Drive.

Display

DATA DISPLAY

Displays specifi c data and operation
data.

Display

AUTO/HAND Display

AUTO

AUTO or OFF Mode (running or stopped).

HAND

HAND Mode

Display

AUTO/HAND Display

RSEQ

RREF

AUTO Mode (running or stopped).

LSEQ

LREF

HAND or OFF Mode.

Display

FUNCTION KEY 2 (F2)

DATA

Press F2 to scroll to the next display.

-->

Press F2 to scroll the cursor to the
right.

DRV/BYP

Press F2 to toggle selection between
Bypass Mode and Drive Mode

Display

BYPASS/DRIVE STATUS

DISPLAY

DRV

(not blinking)

Drive Mode. The bypass will run in
Drive Mode when a Run command
is present.

DRV

(blinking)

Drive Mode, but a condition is
making the bypass run in Bypass
Mode. Example: Smoke Purge -
Bypass Mode

BYP

(not blinking)

Bypass Mode. The bypass will run
in Bypass Mode when a Run com-
mand is present. In a three-contac-
tor bypass, drive input contactor
K1 is open and the drive will be
powered down.

BYP

(blinking)

Bypass Mode with Drive Test Mode
set. The bypass will run in Bypass
Mode when a Run command
is present. In a three-contactor
bypass, drive input contactor K1 is
closed and the drive is powered on.