Z1000u bypass quick start procedure, Troubleshooting, Page 30 of 37 – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 30

Advertising
background image

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure

Z1000U Bypass
Quick Start Procedure

Page 30

of 37

Problem/Symptom

Solution

AL02 Fault in HOA Keypad - BAS interlock Open

Bypass Control Board terminal block TB2-3 to 10 is open.

Close contact TB2-3 to 10.

Problem/Symptom

Solution

FB01 Fault in HOA Keypad – Run Enable/Safety Fault

Bypass Control Board terminal block TB2-2 to 10 is open.

Close contact TB2-2 to 10.

Problem/Symptom

Solution

Drive Will Not accelerate the motor to speed.

U1-01 on HOA keypad indicates 0.00 Hz.

The drive is not receiving a frequency reference.

If the desired reference source is ANALOG: Verify Z1-07 = 1 (Speed
Reference Select is set to Analog Input) and verify analog signals at
terminals.

0 ~ 10 Vdc

4 ~ 20 mA

+

-

E(G)
or
TB5

Cable

Shield

+

-

E(G)
or
TB5

Cable

Shield

+V AC A1 A2 A3 FM AM AC

+V AC A1 A2 A3 FM AM AC

Potentiometer 2kΩ

+V AC A1 A2 A3 FM AM AC

TB3 Typical Analog Frequency Reference Input Connections (Choose one)

If the desired reference source is DIGITAL: Verify Z1-07 = 0 (Speed
Reference Select set to Operator) and Z1-09 = Fref (HAND Mode Drive
Speed Reference) is a non-zero value. Refer to the Bypass Technical
Manual for other reference sources, such as serial communications or
PID.

Troubleshooting

12

STEP

11.3 This section provides information to assist in solving common problems that may

occur during test run operation.