Z1000u bypass quick start procedure, Auto mode operation – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 27

Advertising
background image

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure

Z1000U Bypass
Quick Start Procedure

Page 27

of 37

11.1 Prepare for a test run in AUTO mode by performing these steps.

AUTO mode operation operates the motor by providing the Z1000U Bypass with customer supplied, remote RUN and Speed Reference
commands. Items a. thru e. below are required to operate the Z1000U bypass in AUTO mode:

a. RUN Command (AUTO): RUN command, customer supplied. (STEP 5.1.a)
b. Interlock circuits: 2 each, customer supplied. (STEPS 5.1.b and 5.1.c)
c.

Frequency Reference (AUTO): Reference source, customer supplied. (STEP 7.5)

d. Common parameters are programmed. (STEP 8)
e. Motor rotation direction in DRIVE and BYPASS operation modes are verifi ed. (STEP 9)

11.2 Confi rm these remote AUTO circuits are connected to the Z1000U Bypass to prepare to

perform a test run in AUTO mode. AUTO circuits are customer supplied.

Frequency Reference (AUTO) at Drive Control Board A1:

TB3-A2 (signal) to AC (common) 4-20 mA. Parameter H3-09 = 2. (Factory setting), or

TB3-A1 (signal) to AC (common) 0-10 Vdc. Parameter H3-01 = 0. (Factory setting)

RUN Command (AUTO): AUTO RUN command by contact closure Bypass Control Board TB2-10 to TB2-1.

AUTO Speed Command (Customer supplied)

0 ~ 10 Vdc

4 ~ 20 mA

+

-

E(G)
or
TB5

Cable

Shield

+

-

E(G)
or
TB5

Cable

Shield

+V AC A1 A2 A3 FM AM AC

+V AC A1 A2 A3 FM AM AC

Potentiometer 2kΩ

+V AC A1 A2 A3 FM AM AC

TB3 Typical Analog Frequency Reference Input Connections (Choose one)

AUTO RUN Command (Customer supplied)

Bypass Control
Board

Auto Mode Operation

11

STEP

Advertising