Z1000u bypass quick start procedure, Check motor rotation direction (continued), Ub-01= 0.0a – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 23

Advertising
background image

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure

Z1000U Bypass
Quick Start Procedure

Page 23

of 37

Step

HOA Key Press

Description

HOA Display/Result

9.1. 4

OFF

ON

OFF

ON

CORRECTING Motor Rotation (DRIVE)

Follow sub-steps a. thru f. below
to correct motor rotation
direction in DRIVE mode.

a. De-energize/turn

OFF

and lock out the MAINS
power supply to the
bypass.

b. Turn off power on the

front of the bypass and
open the cabinet.

c.

Verify that there is no
power present in the
bypass.

d. Exchange the wires

connected to terminals
T1 and T2 where the
motor leads are connected
at the motor output circuit.

e. Tighten all connections.
f. Return

to

STEP 9.1.1 to

verify proper motor
rotation in DRIVE.

Step

HOA Key Press

Description

HOA Display/Result

9.1. 5

CHECK Motor Rotation (BYPASS)
WARNING!
Clear debris, tools, and wire clippings from the bypass
enclosure before applying power.

Remove lock-out/tag-out, and energize the MAINS branch circuit supply to
the bypass.

Re-install all covers and close enclosure doors.

9.1.6

OFF

ON

ON

OFF

Apply power to the bypass.

9.1.7

Press F2 to toggle to the Bypass Mode.

The keypad display should show BYP–OFF if the device is ready for
Bypass operation.

UB-01= 0.0A

Freq Ref (AUTO)

UB-02=10000110

UB-03=00001000

E(G)

E(G) IG

IG R+

R+ R-

R- S+

S+ S-

S-

S1

S1 S2

S2 S3

S3 S4

S4 S5

S5 S6

S6 S7

S7 S8

S8 SN

SN SC

SC SP

V+

V+ AC

AC A1

A1 A2

A2 A3

A3 FM

FM AM

AM AC

AC

24V

24V

RP AC

AC

M1 M2 M3 M4

M1 M2 M3 M4

MD ME MF

MD ME MF

M

MA MB MC

MB MC

T1 T2 T3

Motor

T1, T2, T3

Reverse

Motor Leads

T1 and T2

Motor

Output

Circuit

DANGER! Shock Hazard.

De-energize and lock-out MAIN
power supply to the bypass
before contacting motor leads.

To motor

Check Motor Rotation Direction (continued)

9

STEP

Advertising