YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure

Z1000U Bypass
Quick Start Procedure

Page 13

of 37

7.3 HAND REF: Set the HAND Frequency Reference.

The factory default for the HAND Frequency Reference is 10.0 Hz.
Note: Skip this step if a test run at 10.0 Hz ( approximately 300 rpm on a 4 pole motor) is suitable for the application. The HAND
frequency reference is set in parameter Z1-09. Use the following key example to change the frequency reference in HAND mode.

7.4 Example key press procedure.

Step

Key Press

Display

7.4.1

Power-up state

NOTE: The Frequency reference

screen appears after the drive is

energized.

7.4.2

7.4.3

7.4.4

7.4.5

7.4.6

7.4.7

7.4.8

Step

Key Press

Display

7.4.9

7.4.10

7.4.11

or

7.4.12

7.4.13

Confi gure the HAND and AUTO Frequency Reference (continued)

7

STEP