Z1000u bypass quick start procedure – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 13

YASKAWA TOEP YAIZ1D01A Z1000U Matrix Bypass Quick Start Procedure
Z1000U Bypass
Quick Start Procedure
Page 13
of 37
7.3 HAND REF: Set the HAND Frequency Reference.
The factory default for the HAND Frequency Reference is 10.0 Hz.
Note: Skip this step if a test run at 10.0 Hz ( approximately 300 rpm on a 4 pole motor) is suitable for the application. The HAND
frequency reference is set in parameter Z1-09. Use the following key example to change the frequency reference in HAND mode.
7.4 Example key press procedure.
Step
Key Press
Display
7.4.1
Power-up state
NOTE: The Frequency reference
screen appears after the drive is
energized.
7.4.2
7.4.3
7.4.4
7.4.5
7.4.6
7.4.7
7.4.8
Step
Key Press
Display
7.4.9
7.4.10
7.4.11
or
7.4.12
7.4.13
Confi gure the HAND and AUTO Frequency Reference (continued)
7
STEP