Step

HOA Key Press

Description

HOA Display/Result

9.1. 8

then

Press HAND then quickly press OFF within 1 second. The motor will briefl y
spin under line power.
Observe the motor and verify correct rotation direction.
Verify no faults or alarms occur.

The HAND LED turns OFF and the motor coasts to stop.

Proceed to STEP 10.1 if motor rotation in BYPASS Mode is correct.

Otherwise, proceed to STEP 9.1.9 if motor rotation in BYPASS is NOT
correct.

9.1.9

OFF

ON

OFF

ON

CORRECTING Motor Rotation (BYPASS)

Follow sub-steps a. thru f. below to correct motor rotation direction in BYPASS mode.

a. De-energize/turn

OFF

and lock out the MAINS
power supply to the
bypass.

b. Turn off power on the

front of the bypass and
open the cabinet.

c.

Verify that there is no
power present in the cabinet.

d. Exchange the wires

connected to terminals
L1 and L2 where the
input power is connected
at the input circuit breaker.

e. Tighten all connections.
f. Return

to

STEP 9.1.5 to

verify proper motor rotation
in BYPASS.

DANGER! Shock Hazard.

De-energize and lock-out MAIN
branch circuit power supply to the
bypass before contacting conductors.

MAINS

L1, L2, L3

Input

Circuit Breaker

OFF

De-energized

1

2

Reverse

Mains

L1 and L2

Wires

1L2, 1L2, 1L3

LOAD

To internal bypass circuit

From

Branch Circuit

Check Motor Rotation Direction (continued)