Installation to metallic surface, Thermal compound, 3 conditions of acceptability – Yaskawa V1000 Finless Type User Manual

Page 9

Advertising
background image

3 Conditions of Acceptability

YASKAWA ELECTRIC TOBP C710606 21E YASKAWA AC Drive - V1000 Finless Installation Guide

9

Figure 2

Figure 3 Output of Heatsink Plate Temperature by Analog Output

Note: 1. Accuracy of the temperature reading may vary

±5 ºC between 50 and 100 ºC.

2. The heatsink temperature is affected by the ambient temperature. Never exceed the allowable maximum

heatsink plate temperature.

Drive Overheat Alarm (oH)

Use parameter L8-02 to cause the drive output an alarm when the heatsink plate exceeds the

specified temperature.
L8-03 determines the action taken by the drive when an oH alarm is triggered. Refer to the

V1000 Technical Manual for more details.

Installation to Metallic Surface

The mating surface shall have the following properties:

• Surface flatness shall not exceed 0.2 mm across the entire mating surface.

• Surface roughness shall not exceed 25 S.

Note: A surface roughness of 25 S means “Ra” (average roughness) is not greater than 6.3 a and “Ry”

(maximum peak) is not greater than 25

μm.

Thermal Compound

Apply a thermal compound between the heatsink plate and the mating surface. The thermal

compound assists in drive heat dissipation.
Yaskawa recommends the thermal compounds in

Table 2

.

0

Output Voltage㧔V㧕

10.0

9.0

5.0

90

50

100 Temperature(°C)

Advertising