Yaskawa J7 Drive User Manual
Page 37

5-2
A.
n16
: Accel Time 1
Factory setting (each):
10.0
seconds
n17
: Decel Time 1
Range (each): 0.0 to 999 seconds
n18
: Accel Time 2
Factory setting (each):
10.0
seconds
n19
: Decel Time 2
Range (each): 0.0 to 999 seconds
The Drive incorporates two sets of individually programmable acceleration and deceleration times.
Setting resolution is 0.1 seconds when set to less than 100 seconds; resolution is 1 second when set
to 100 seconds or more.
B.
n36
thru
n39
: Multi-
Data
11
: Accel/Decel Time Selection
function Inputs (Term. S1 thru S5)
By programming data " 11 " into one of the multi-
function parameters (
n36
thru
n39
), one of the multi-
function input terminals (S2 thru S5) becomes a time
selection input. When the input terminal (i.e. external
contact) is open, Time 1 (
n16
/
n17
) is selected. When
the input terminal is closed, Time 2 (
n18
/
n19
) is
selected.
TIME 1 o
o
o
TIME 2
S5
SC
0V
5.2 ACCEL/DECEL TIME