Yaskawa J7 Drive User Manual
Page 59

5-24
Continued
E.
Data
34
: Up/Down Function
Programming data " 34 " for
n39
(multi-function input terminal) allows the S4 / S5 inputs to be used
for Up/Down frequency setting.
NOTES:
1. Parameter
n38
will not be valid when
n39
is set to " 34 ".
2. Jog has priority over Up/Down.
3. Up/Down has priority over Multi-step Frequency inputs.
4. Upper limit speed is set by the formula:
n09
(Fmax) x
n30
(Freq. Ref. Upper Limit)
100
5. Lower limit speed is from
n31
, Frequency Reference Lower Limit.
6. See section 5.10 for information on the Up/Down hold memory.
EXAMPLE:
n39
Data
34
: Up/Down function
DRIVE
S4
UP
S5
DOWN
SC
0V
UP
o o
DOWN
o o
INPUT SIGNAL
Term. S4 Term. S5
FUNCTION
UP DOWN
Open
Open
HOLD
Closed Open
UP (Frequency command approaches frequency
command upper limit)
Open
Closed
DOWN (Frequency command approaches minimum
output frequency or frequency command lower limit,
whichever is larger)
Closed Closed
HOLD
5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)