Yaskawa V1000 Option Dual Port EtherNet/IP SI-EN3D/V Technical Manual User Manual

Page 34

Advertising
background image

Error Code

Description

0x24

Attempting to write while the drive is storing data.

Note:

Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor

data using the MEMOBUS/Modbus message area.

u

Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 151 (0x97)

Input Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

151

0

0

Faulted

Alarm

Ready

Speed

Agree

Reset

REV

Running

ZSP

Running

1

Multi-

Function

Photo-

coupler 2

Multi-

Function

Photo-

coupler 1

Multi-

Function

Digital

Output

LOCAL/

REMOTE

Uv

oPE

1

2

Output Frequency (Low Byte)

3

Output Frequency (High Byte)

2

4

Torque Actual (Low Byte), not supported

5

Torque Actual (High Byte), not supported

3

6

Current Actual (Low Byte)

7

Current Actual (High Byte)

Name

Description

Running

Running

0: Stop

1: Forward or Reverse Running

ZSP

Zero Speed

0: Running

1: Stop or DC Injection Braking

REV Running

Reverse Running

0: Not Reverse Running

1: Reverse Running

Reset

Reset

0: No Reset

1: Reset

Speed Agree

Speed Agree

0: No Speed Agree

1: Speed Actual at speed reference

Ready

Drive Ready

0: Not Ready

1: Ready

Alarm

Drive Alarm

0: No Drive Alarm

1: Alarm

Faulted

Drive Fault

0: No Drive Fault

1: Fault

OPE

OPE Fault

0: No oPE Fault

1: oPE

UV

Undervoltage

0: No Undervoltage

1: Undervoltage

LOCAL/REMOTE

Status of Run command from Network

0: Run command is not from network

1: Run command is from network

Multi-Function Digital

Output

Terminal MA/MB

0: MA/MB OFF

1: MA/MB ON

This function is enabled only when H2-01 is set to F.

Multi-Function

Photocoupler 1

Terminal P1

0: Terminal P1 OFF

1: Terminal P1 ON

9 Input Assemblies (Drive Produces)

34

YASKAWA SIEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Technical Manual