Flow sensor setup – Irritrol MC-E User Manual

Page 36

Advertising
background image



Flow Sensor Setup

Flow Sensor Overview

The flow sensing system in the MC-E is designed to reduce the risk of flood damage and water waste. As previously

described, the controller requires a properly sized flow sensor in the system. Also, (connected to Station #2 which must be

converted to Flow Alarm) a normally-open master valve is required.

In the SETUP procedure all stations must be set to “MV=ON”.

The controller has an adjustable flow delay, with a default length of 1 minute, to allow the flow to “settle” after a valve

opens. After each valve’s delay period, (settable from 1 to 9 minutes) the controller will monitor the sensor reading.

Because of delay times and the length of the automatic flow diagnostic procedure, station times under 3 minutes

are not recommended when using flow sensing.

The controller can “learn” the correct flow for each irrigation zone in the system. Also, the maximum acceptable flow

limit for the main line can also be set. With the above in place, the MC-E can detect an overflow condition for a particular

valve in operation (compared to its learned flow) and shut it off. If the controller can cure the flow problem by turning off

the offending station, it will identify the station with the flow error in its display, illuminate the FLOW ALARM light on

its face panel and beep once every 30 seconds to alert the user. Before moving on to the next station in the program, the

controller will check flow in the main line with all valves off. If no flow, the controller moves on. If flow is detected with

no stations on (catastrophic flow), in addition to the alerts above, the controller will energize and close the normally-open

master valve to shut off the irrigation main line.
While the controller is in AUTO/RUN

, but idle, any detected flow with no valves on will also energize station #2

for shut down. Even if you turn the controller to Rain Off

, the MC-E will continue to energize station #2 to keep the

normally-open master valve closed. To clear the flow alert and allow the master valve to open, turn the dial to
FLOW SENSING

and press

.

Use either STATION TEST

or MANUAL to sequence through the stations or to operate a suspect station as you

visually locate the cause of the over flow or unscheduled flow condition. To allow for searching and testing, flow sensing
is not active in STATION TEST

or MANUAL modes.

CAUTION: Flow sensing is active in the controller’s automatic mode for detecting overflow conditions in

the remote control valves and mainline catastrophic flow. Other water outlets in the irrigation mainline will cause

unscheduled flow and activate mainline shutdown. To operate quick coupler valves, etc. downstream of the flow sensor,

either disable flow sensing or manually turn on an unused station that has no learned flow. During operation of a station

with no learned flow, flow sensing is disabled.

When the controller is in RAIN OFF

, flow sensing is disabled.

Enable/Disable MC-E Flow Sensing

Step 1 – Place the Function dial to the FLOW SENSING

position.

Step 2 – If Flow Sensing is not Enabled, the controller will prompt

“Enable Flow? Press DAYOFF”. Press the

button to activate

flow sensing. The K Value/Size Code screen will be displayed when

flow sensing is successfully enabled:

Step 3 – Deactivate flow sensing by pressing the

button.

Offset Value

Flow Unit

K Value

Size Code

Advertising