3 technical data – KACO blueplanet 1502xi User Manual

Page 18

Advertising
background image

Page 20

blueplanet Operating and Installation Instructions 1502x - 2502x

Technical Data

3 Technical Data

Input – Electrical data

Model

1502x

2502x

DC rated power

1600 W

2650 W

Max. recommended
PV generator power

2000 W

3000 W

MPP range

125-400 V

200-450 V

No-load voltage

550 V

550 V

Monitoring input voltage

Stand-by from

V

in

< 125 V

Stand-by from

V

in

< 200 V

Max. DC input current (Isc)

21.45 A

21.45 A

Polarity safeguard

Short-circuit diode

Table 4:

Input - Electrical data

* Feed-In only, if PV-Voltage is smaller 550 V

Output – Electrical data

Model

1502x

2502x

Rated power

1500 W

2500 W

Maximum power

1650 W

2500 W

Line voltage

212 V-264 V @ 240 V

AC

184 V-228 V @ 208 V

AC

Rated current

6.5 A @ 240 V

AC

7.2 A @ 208 V

AC

10.4 A @ 240 V

AC

12.0 A @ 208 V

AC

Max. current

8.0 A @ 240 V

AC

8.0 A @ 208 V

AC

12.0 A @ 240 V

AC

12.5 A @ 208 V

AC

Power factor

≈ 1

Rated frequency

60.0 Hz

Frequency range

59.3 Hz-60.5 Hz

Distortion factor according to
VDE0838 part 2
(EN 61000-3-2)

< 3 % at rated power

< 5 % over the entire range

Fault signal relay

Potential-free NO contact (make contact), max. 30 V / 3 A

S0 output

Open collector-output max. 30 V / 50 mA

Overvoltage protection

Varistors and spark gaps

Table 5:

Output - Electrical Data