Danger, 3 external dc switch and ac disconnect – KACO blueplanet 1502xi User Manual
Page 24
 
Page 26
blueplanet Operating and Installation Instructions 1502x - 2502x
Installation and Start-Up
nect, suitable for use for the prevailing conditions, and limits 
the grouping of disconnects to six per enclosure. Section D, 
permits utility interactive, or grid tied inverters to be located 
in areas that are not readily accessible, and details the switch 
requirements. The AC and DC disconnect should be line of sight 
with the inverter and be readily accessible.
690.15: The means for disconnecting all aspects of a solar elec-
tric system must be provided, and if the equipment is energized 
from more than one source, the disconnecting means should be 
grouped and identifi ed. Allowances for several AC circuits to 
be disconnected is allowed as long as the disconnect complies 
with 690.17 
690.17: The means for disconnect all ungrounded conductors 
should be readily accessible, externally operable with expos-
ing the operator to live circuits, and plainly indicate the open 
and closed positions. The disconnect shall have an interrupting 
rating suffi cient for the nominal circuit voltage and current that 
is available at the line terminals of the equipment.
690.64: The supply side of the inverter shall be permitted to 
be connected to the supply side of the service disconnecting 
means as permitted in 230.82.6. The load side is permitted as 
long as each interconnection is made with a dedicated circuit 
breaker rated for the appropriate current back feed rating.
230.82.6: The type of equipment connected to the supply is 
listed, with subsection six identifying solar electric systems as 
permissible. 
All components within a UL 1741 compliant inverter must pass 
evaluation spacing, voltages and currents that the inverter is 
rated for. The UL 508 standard, industrial control equipment, 
auxiliary devices has provisions for testing manually operated 
switches. The integrated switch passed the UL508 standard 
under the fi le E304888 for use within a UL 1741 approved grid 
tied inverter. The switch was tested 6000 operating cycles at 
the nominal AC and DC voltages and currents as noted in table 
one below. Additional operating cycles of 4000 resulted in a 
total of 10000 successful operating cycles. The switch was de 
constructed and evaluated under a pass fail criteria. 
As referenced in the NEC, subsection 690.17, the switch must 
meet applicable voltage and current ratings. The AC and DC 
switch ratings are detailed in this table:
AC / DC 
Disconnect
Inverter Models
1502
2502
DC Nominal 
Voltage: VDC
550
550
DC Nominal 
Current: IDC
21.45
21.45
AC Nominal 
Voltage:
VAC
240/ 208
240/ 208
AC Nominal 
Current:
IAC
8
12.5
5.3 External DC switch and AC
disconnect
NOTE
External DC switch
An external all-pole DC disconnect switch and an AC dis-
connect, which allows for the inverter to be disconnected 
from the photovoltaic generator and the AC power grid and 
removed for service.
!
DANGER
When replacing the inverter section, the installer 
must turn off the switch in the connection box, lock 
it and measure the AC and DC wiring to be sure it 
is not energized.
!
DANGER
If there is a ground fault in the PV array, the groun-
ded conductor may be live. This is a problem with 
the requirements of the National Electric Code 
requiring that only the ungrounded conductor be 
switched. If a ground fault is present and the GFDI 
fuse blows, the grounded conductor is no longer 
grounded and is live with respect to the position of 
the ground fault.
Safety of components
The Authority Having Jurisdiction (AHJ) has a diffi cult charge 
and maintains ultimate authority of the solar electric system’s 
fi nal inspection. The AHJ must be well versed with the require-
ments of the NEC, understand the local utilities’ ruling on the 
use of a utility external disconnect switch (UEDS), and appli-
cable use of a UL 1741 approved product.
The following NEC 2008 subsections provide an overview of 
the solar electric system disconnect requirements: 690.13; 
690:14, 690.15, 690.17; 690.64, 230.82.6. Subsections are 
summarized below. For the complete text refer to the appli-
cable NEC version approved for use in your jurisdiction. 
690.13: The means to disconnect all current carrying conduc-
tors of a solar electric system from all other conductors in a 
building. 
690.14, sections A through D: Section A, the disconnection 
means are not required to be suitable for service equipment and 
should be rated in accordance with 690.17. Section B, equip-
ment specifi c to the photovoltaic source circuits such as over 
current devices, circuit isolation switches, and blocking diodes 
are permitted on the solar electric side of the disconnection 
means. Section C, the disconnection means should be located 
in a readily accessible location, preferably near the points of 
building entrance, be marked as a solar electric system discon-