Page 30

blueplanet Operating and Installation Instructions 1502x - 2502x

Installation and Start-Up

5.6 Electrical connection

General information

The electrical connections can be established after the inverter
is installed in its fi xed location. Knockouts are provided on the
sides, bottom, and rear of the inverter bottom plate to easily
run conduit to the desired locations.

NOTE

Only conduit pipes according to UL 514 B can be used.
Guide the wiring through the conduit pipe.

!

WARNING

Inputs and output circuits of this unit are isolated
from the enclosure. System grounding must be done
in accordance with the National Electrical Code
(NEC), ANSI/NFPA 70 and is the responsibility of
the installer.

You must adhere to all mandatory safety regulations, the
currently required technical connection specifi cations of the
responsible power supply company, as well as to other gener-
ally applicable regulations.

!

WARNING

To connect the inverter, the AC and DC sides must
be disconnected from all power sources and secu-
red against being inadvertently energized.

Country setting on the display: USA 240 V no neut

L1

L2

L3

120°

120°

120°

~

=

~

=

~

208V

208V

208V

120V

120V

120V

N

=

Figure 18: 208 V / 120V WYE

Country setting on the display: USA 208 V

L1

L2

L3

120°

120°

120°

~

=

~

=

~

208V

208V

208V

=

Figure 19: 208 V Delta

Country setting on the display: USA 208 V no neut

L1

L2

L3

120°

120°

120°

~

=

~

=

~

480V

480V

480V

L1

L2

L3

120°

120°

120°

=

~

480V

480V

480V

=

Figure 20: 480 V Delta or 480 / 277 V WYE

!

WARNING

Do not connect the inverter to the 480 V Delta or
480 V / 277 V WYE power grids.