blueplanet as Part of a PV Installation
7.2 Installation with multiple inverters on a three phase system
Observe the following regarding installations with multiple inverters on a three phase system:
Asymmetric grid-feed:
The power should be distributed as equally as possible over the three phases. In the US, typically the asymmetry between the phases may 
be a maximum of 6 kW (This number can vary depending on utility transformer size and codes).
Figure 29: Three phase grid connection for installa-
tions with multiple inverters
Electrical connection:
The blueplanet feeds only on two phases. In order to avoid asymmetries on a 3 phase grid, installations with multiple inverters should 
be designed so that the inverters feed into the grid in differing phases. The inverter feeds into the connections labelled L1 and L2. If you 
have multiple inverters, connect the actual phases L1 and L2 to terminals L1 and L2 on the fi rst unit. On the second unit, connect phases 
L2and L3 to terminals L1 and L2. On the third unit, connect phases L3 and L1 to terminals L1 and L2. Continue as above. This distributes 
the power optimally.